Navigator protocol analysis

This page documents confirmed findings from the static analysis of the Navigator client and from the read-only validation of a Navigator 10 installation. It is not a complete protocol specification.

Confirmed local communication

  • Modbus TCP: port 502, unit/slave ID 1.
  • Local HTTP interface: port 80.
  • Navigator 10 WebSocket: port 61220.
  • WebSocket authentication through the local PIN as auth_code.
  • Navigator 2.0 web access: local HTTP on port 80, form login with a CSRF token and the local network code.
  • For the implemented web access, Navigator Pro uses the Navigator 10 WebSocket variant.
  • Web data is delivered as typed values with units or as a translated status.

The integration therefore keeps Modbus as the base path and uses the local web interface only as an optional supplement or fallback. No cloud logins are required.

Detection and reconnection

During setup, reconfiguration and repair, the variant Modbus makes most likely is tried first, and on failure the other local variant is tried as well. Only the client that actually succeeded is stored. In normal operation that session is reused. After session or transport errors the same protocol client is rebuilt; the other Navigator generation is deliberately not activated on a trial basis. A renewed detection of both variants happens through reconfiguration, or for as long as no reliable variant has been stored yet.

Details: Local Navigator Web Interface.

Installation validation

The validated installation was detected as Navigator 10. The corrected API detector finds only heating circuit A there. The registers of the heating circuits that are not configured do answer, but they return the sentinel value -1.0.

On this installation the cascade probe at address 1147 answers with the raw word FFFF, that is UCHAR 255. That value means "not available" and must not enable the optional cascade register group. As a result the detected map on this installation dropped from 170 to 153 definitions.

Across 309 read-only batch/single comparisons over 170 definitions and 45 groups there was no raw value deviation. The reported values 254, 255 and -1.0 were register-specific not-available sentinels. Room operating modes are still secured individually, because other Navigator 2.0 reports have shown plausible but deviating batch values.

The local web client returned 60 normalized values, among them temperatures, pressures, runtimes, energy amounts, status values and the software version. No PINs, tokens, IP addresses, serial numbers, account IDs or raw responses are stored in the repository.

Findings from the EXE analysis

Identified were several Navigator generations, UDP discovery for older variants, further TCP/TLS communication paths, live events such as NC_CHANNELDATA, typed channel values, as well as dynamic channels, parameters, rooms, errors, translations and virtual channels.

A capture session on 2026-09-27 additionally decoded the configuration database of the Windows service tool ("IDM Smart Navigator" 2.3.118). Its files under %APPDATA%\NAVudpClient are obfuscated with a 3-byte XOR key; the decoded tables contain:

Table Entries Content
channels 306 measurement channels: alias, German description, unit, bitmask/state lists, firmware signal names
parameters 2329 controller parameters (hparam/iparam/vparam) with defaults, per-machine defaults and selection values
errors 2005 error codes with component and error-kind enums plus user/service descriptions (see next section)
topics 46 view grouping of the channels
translations 16392 enum texts; German is complete, English is not shipped for the device enums

The UDP live protocol of the older modules (ports 20001, 20999 and 54551 named in the binary) is not answered by a Navigator 10 web module; those ports belong to the historical UDP live streaming of older NAV generations. Device discovery in the current apps runs through the myIDM cloud, not through local UDP broadcasts.

The concrete UDP wire format (scalings, byte orders, special types such as UDP_FUNCFLOAT) remains undetermined; no integration code depends on it.

Error-code database (service tool capture, 2026-09)

The decoded service tool configuration contains the complete vendor error-code database. The numbering:

  • 0 — "no error" placeholder;
  • 20..999 — controller messages and errors. This is the range the Modbus internal_message register reports (020–999); 366 codes exist there, 343 of them with German component texts;
  • 10000+ — device-side error blocks: 20000 display, 30000+ outdoor unit, inverter, fan, EVD, Carel peripherals and cascade devices (1637 codes).

Each entry carries the affected component (text, for example Wärmepumpenvorlauf) and, where the vendor has one, the error kind (info, for example Maximaltemperatur). "{text} {info}" reproduces the controller display wording. 1160 entries carry German user descriptions and 1346 carry German service remediation texts; English does not exist for these enums.

Validation against the integration: every one of the 90 exact codes of the hand-collected internal_messages.py table exists in the database with a semantically identical text, and the composed wording matches (code 20 Wärmepumpenvorlauf Maximaltemperatur, code 100 Außentemperatur + Kurzschluss). The numbering is therefore confirmed to be the same namespace the Modbus register reports.

Since idm-heatpump-api 2.6.0 the database is packaged as read-only metadata (get_error_code_info()), regenerable through the API repository's scripts/generate_error_codes.py. The capture itself — which also contains PINs, serial numbers and network data — is never committed. Six entries with sub-error-bit breakdowns (extras) exist in the source and are dropped from the packaged form.

Deliberately not implemented

  • myIDM cloud login, cloud polling and installation management
  • firmware, configuration and SD card writes
  • fixed UDP ports or guessed binary packets
  • guessed channel meanings, units or scaling factors
  • undocumented Modbus writes

Further protocol work needs anonymized local responses or recordings with the channel ID, name, unit, scaling, data type, room assignment and live event. Before committing, PINs, tokens, network data, serial numbers and owner data must be removed.

Note on the KNX example project file (.knxproj)

Occasionally an IDM-specific ETS project file is available (named something like KNX_NAVIGATOR_2_0_Beispielprojekt.knxproj). That file describes the KNX gateway (typically a Weinzierl KNX IP BAOS 774) and the communication objects enabled on it. It is not a reliable source for IDM model or firmware detection.

What the .knxproj file does NOT provide

  • no IDM heat pump model
  • no IDM Navigator generation (Navigator 2.0 / 10 / Pro)
  • no IDM firmware or software version
  • no IDM serial number

The metadata it contains, such as ApplicationVersion="16", VersionNumber="256", MaskVersion="MV-07B0", SerialNumber="KNX IP BAOS 774", the project name ("KNX Navigator 2.0") and device names ("IDM NAV2.0 KNX IP Gateway"), identifies the KNX gateway and the ETS project only. It must never be adopted as IDM firmware or an IDM model. Free-form labels such as "Navigator 2.0" in the project name are no substitute for a Modbus or web detection.

What the .knxproj file does provide

The enabled communication objects are a valuable completeness and naming reference. A corrected full evaluation of that example project file (as of 2026-07-27, 726 active objects) was cross-checked on the same day by a strictly read-only live check on a Navigator 10 installation. All hypothetical assignments were confirmed:

KNX object ETS name (partly with typos) API register Address Type Live value
995 Photovotaik Surplus pv_surplus 74 FLOAT kW plausible
996 Photovotaik current pv_production 78 FLOAT kW plausible
992 Home Consumption house_consumption 82 FLOAT kW plausible
993 Battery Discharge battery_discharge 84 FLOAT kW plausible
994 Battery state of charge battery_soc 86 INT16 % −1 = sentinel
997 Total electric output power_consumption_hp 4122 FLOAT kW plausible
998 Current thermal output thermal_power_flow_sensor 4126 FLOAT kW plausible
999 Total thermal energy total_heat_energy 4128 FLOAT kWh plausible

Additionally confirmed: electric_heater_power (address 76) and pv_target_value (address 88) are contained in the API, but are not active in the example project.

Important rules of interpretation

  • KNX object number ≠ Modbus address (the numbers 992–999 are not addresses).
  • KNX DPT ≠ Modbus data type (for example, battery_soc is a single signed INT16 register, not a two-register float).
  • KNX write flag ≠ Modbus write permission. An enabled write flag only means that the object accepts telegrams from the bus; it is no evidence of a safe Modbus write.
  • battery_soc sentinel: the raw value 65535 (unsigned 16-bit) has to be decoded as signed −1 and means "not available". A UINT16 decoding would wrongly display 65535 %.

Consequence for this integration

Model and firmware detection stays exclusively with Modbus (detect_model()) and the optional local web supplement. There is no code path that evaluates ETS or BAOS metadata. The corresponding regression tests are in tests/test_knx_evidence.py. Adding new registers or write services is not justified from this file alone; see the section "Deliberately not implemented".

IDM controller ID spaces

On an IDM Navigator controller, one physical quantity is addressed by up to three independent ID spaces. These spaces overlap semantically, but they are not 1:1, and the numbers are deliberately different. They must never be used as interchangeable addresses.

ID space Used by Heating example PV surplus example
Modbus register external protocol, through idm-heatpump-api 1748 74
Internal stats ID statistics engine, SD card (stats/amount/<id>_v1.csv, last_values.json) 477 495 (cumulative: 100495)
KNX communication object ETS example project (Weinzierl BAOS 774) 400 995

What that means in practice

  • KNX object number ≠ Modbus address (already stated in the KNX section).
  • Internal stats ID ≠ Modbus address. Example: heating energy has the internal stats ID 477, but the Modbus address 1748. An error message of the form "Stat 477" on the controller display therefore corresponds to the Modbus value at address 1748, and not to a gap in the Modbus address space.
  • Internal stats ID ≠ KNX object number. Example: PV surplus has the internal ID 495, but object number 995 in the KNX example project.
  • Cumulative stat IDs in the 100000 range (for example 100495) are the daily totals of the underlying series (495), not a physical quantity of their own.

Syscount cross-reference (energy registers)

The file syscount.ini on the SD card contains the semantic names of the cumulative counters. This integration keeps a cross-checked mapping table in custom_components/idm_heatpump/controller_stats_reference.py. It is documented incompletely on purpose: only registers cross-checked through at least two of the three ID spaces are included.

Syscount key Stats ID Library register Modbus KNX object Meaning
ZQHPH 477 energy_heating 1748 400 Heat quantity, heating (heat pump)
ZQHPP 471 energy_dhw 1754 402 Heat quantity, domestic hot water / priority
ZQHPD 472 energy_defrost 1756 403 Heat quantity, defrost
ZQHPC — energy_cooling 1752 401 Heat quantity, cooling
ZQELH — energy_electric_heater 1762 406 Heat quantity, electric heating element
ZQHPO — total_heat_energy 4128 999 Heat quantity, total (Nav 10)
— 495 pv_surplus 74 995 Photovoltaic surplus
— 496 pv_production 78 996 Photovoltaic power
— — house_consumption 82 992 House consumption
— — battery_discharge 84 993 Battery discharge
— — battery_soc 86 994 Battery state of charge (INT16, -1 = n/a)
— — power_consumption_hp 4122 997 Total electrical power
— — thermal_power_flow_sensor 4126 998 Thermal power

Use in the diagnostics export

The integration's diagnostics export (Download diagnostics on the integration page) contains the cross-referenced syscount key for every known energy register. That allows a plausibility comparison between the Home Assistant reading and the controller's own counter without removing the SD card.

Limits of the finding

This table was collected on a confirmed Navigator 10 installation (firmware NAV10_20.24-880-g265e09c4a). Navigator 2.0 and Pro may use different stats IDs; the syscount key names, by contrast, should be generic. New entries always require a cross-check through at least two of the three ID spaces (Modbus + syscount, or Modbus + KNX).

SD card structure (Navigator 10)

An SD card from a Navigator 10 typically contains the following usable structures:

/
├── log/raw/<controller_id>/<YYMMDD>.mal   # binary daily logs, proprietary
├── recovery/
│   ├── Backup/config/<YYYY-MM-DD_HHMM>/   # daily 02:00 snapshots
│   └── autosaveconfig_<controller_id>--<id>/config/<YYYY-MM-DD_HHMM>/
└── update/backup/backup<YYYYMMDDHHMMSS>.iup   # firmware backup packages

The snapshot of a configuration backup contains, among other things:

File Content Usable for
syscount.ini cumulative counters (ZQHPH, ZQHPP etc.) semantic cross-reference
stats/amount/<id>_v1.csv daily time series per stats ID plausibility comparison
stats/amount/last_values.json last cumulative value per stats ID plausibility comparison
stats/amount/heating.csv, priority.csv named daily time series plausibility comparison
stats/energy/ba_energy_hp, ba_energy_eh binary energy and heating element blocks structural reference
stats/pv/ba_pv binary PV daily time series (9 columns) structural reference
stats/runtimes/ba_runtimes, bivalence_runtimes binary runtime statistics structural reference
zone.ini configured zones (size=0 = none) detection consistency
heatpump.ini error buffer position (no serial!) low value
frwaparam.ini firmware parameters (FRW*/FRWA*) low value
hparam.ini, iparam.ini heating/installation parameters do not commit (installation specifics)
errorLogBuffer.ini, paramLogBuffer.ini error and parameter logs do not commit

This integration does not read the SD card. The structure above is documented for support purposes only; when users want to compare values, they can check the corresponding CSV files manually against their HA sensors.

The Navigator 10 web interface speaks a WebSocket protocol on port 61220. Every frame has the form {"controller": "<name>", "command": "<verb>", "data": {...}}. Authentication happens through the query parameter ?auth_code=<PIN> when the connection is established.

The following table is the result of a strictly read-only live exploration (overview/detail only) on a confirmed Navigator 10 installation (firmware NAV10_20.24-880-g265e09c4a, July 2026). It replaces the earlier, incomplete picture from the static EXE analysis.

Supported controllers

Controller Commands Meaning
status overview authorization status ({"authorized":true})
home overview, detail home screen status (frost protection info, auth active, demo mode, header) and detail data including energy flow (PV, house consumption, grid)
system overview system detail block (energy amounts today, type dictionary)
system.freshwater overview DHW detail (circulation, StatusInfo, SystemMode, temperatures)
setting detail, save, execute read settings (detail), write them (save), trigger actions (execute)
statistic overview, detail statistics blocks
cascade overview cascade information (empty response on a single-unit installation)
notification overview, save message overview, message change
authentication overview, save system information (buffer.systemMode, temperatures, energyflow); level login through save with userlevel and code
showcase overview demo and info sequences
frostprotection overview frost protection wizard (only active in a frost situation)
relaytest overview relay test wizard (only active in a service situation)

Sub-controller pattern: the system.* sub-controllers (for example system.freshwater) use parameterId instead of settingId in the data block. The library currently uses only setting/detail, home/detail, statistic/detail and notification/overview.

Setting action types (through setting/execute): the SPA code assigns settings to certain UI components based on their type field. Known action types are restart, actioncode, execute, relaytest, tt1, ttw, ttboost. execute is the generic "trigger action" type, which starts the function stored in the setting on the server side. The "restart display" button, for example, is implemented as a setting of type restart and is triggered through setting/save with the corresponding setting ID.

Unsupported controllers

The following controller names were tried and were explicitly rejected as unsupported by the Navigator 10 (provided controller [...] is not supported!):

controller        firmware         update          upgrade
software          usb              upload          maintenance
system.update     system.firmware  system.software system.usb
does.not.exist    (negative control)

Consequence: firmware update

The Navigator 10 WebSocket interface offers no update endpoint. The same is true for the HTTP interface (port 80, a pure SPA with no server-side update routes) and for Modbus TCP (port 502). The controller's three local interfaces cover normal read/write operation, but no firmware operations.

Firmware updates on the Navigator 10 accordingly happen through:

  1. the myIDM cloud portal (app.myidm.at) — the canonical web interface the framework calls the "IDM web interface". Push updates usually arrive automatically through this channel.
  2. a USB stick through the controller display's service menu (installer level). The integration calculates the time-dependent installer level codes (L1/L2) and offers them as optional sensors. On the display itself one can then look for an "Update" / "Software" / "USB" menu item.

Exploration notes for support

When users ask about firmware updates, the answer is clear:

  • Locally through the web interface or the WebSocket: not possible, the device rejects all update controllers.
  • Cloud (myIDM): the primary update channel.
  • USB plus display: the secondary service channel.

Extending the integration with its own update functions is not planned and would require deliberately including cloud functions (see the section "Deliberately not implemented").

User levels, codes and access parameters

Verified on 2026-09-27 against a second, independent Navigator 10 installation (web module firmware of June 2026, jsonVersion 11), strictly read-only apart from rejected login attempts:

  • The WebSocket knows exactly two levels: userlevel 0 (end user, unlocked by the local network PIN) and userlevel 4 (technician/expert). The device explicitly rejects levels 1–3 ("specified userlevel [n] is not supported!").
  • The level login is authentication/save with {"userlevel": 4, "code": …}; a wrong code answers {"authorized": false} without dropping the connection. Repeated wrong entries block the code input on the controller for a while (parameter N2_USERLEVELINPUTBLOCKED).
  • The time-dependent installer codes L1/L2 that this integration computes are valid only on the controller display's service menu. Tested on the WebSocket: neither the end-user PIN nor correctly computed L1/L2 codes are accepted for userlevel 4. The WebSocket technician code is a separate, per-installation code (display menu CODE_ENTRY_EXPERT), which IDM distributes only through its service partners.

Access-relevant controller parameters (from the decoded parameter table):

Parameter Meaning
SYSLPIN local network code (WebSocket/HTTP PIN); 0 blocks local access
CODE_ENTRY_EXPERT technician code entry (display menu, per installation)
SYSSSC simple service code (display/older modules)
SYSDPTO display PIN timeout
T13_CODE_VOREINST_1 / T21_CODE_VOREINST_2 factory presets of the technician code

Controller clock: on the capture installation the controller clock ran about two hours ahead of local time (most likely a doubly applied daylight-saving offset). The L1/L2 codes are derived from the time shown on the controller display, not from the querying computer's clock — always verify the display time first.

Also confirmed in the same session: setting/detail without a settingId answers "data is empty!", the frostprotection and relaytest wizards answer "wizard is not available!" outside their situations, and status/overview reports userlevel, myidmInfo, the notification count, jsonVersion and the controller clock (timestamp).

myIDM cloud API (reference)

The myIDM cloud (app.myidm.at, www.myidm.at, a.myidm.at) is IDM's canonical telemetry and control channel. The integration does not use it (see "Deliberately not implemented"), but the following findings were verified in July 2026 through a strictly read-only live login (only /api/user/login + /api/installation/values, no /api/installation/command) and are documented here as a reference to make future research easier.

⚠️ Legacy API (verified for 2022–2026)

The API documented here is the old v0 API, which has been in use since at least 2018 (Tom Beyer, beyer.app) and was fully reverse-engineered in 2022 by the ioBroker adapter lonestar2001/ioBroker.idm. It still works as of July 2026, but it must be assumed that IDM will shut it down in the medium term in favor of the new OAuth2 API (see below).

Endpoints (all under https://www.myidm.at)

Endpoint Method Purpose Body (form-urlencoded)
/api/user/login POST login, session token + installation list username=<email>&password=<sha1(password)>
/api/installation/values POST read the current values of an installation token=<token>&installation=<id>
/api/installation/command POST change the mode (system/circuit) token, installation, command, value, optionally circuit

Important:

  • User-Agent: IDM App (iOS) (or Android) has to be set, otherwise the server sometimes does not respond.
  • The password is sent as a SHA1 hex hash (an outdated scheme, no salt, no TLS pinning).
  • The domain's SSL certificate has historically had chain problems; some clients (ioBroker, for example) therefore disable verification.

/api/user/login – response structure

{
  "token": "<64-character hex string>",
  "installations": [
    {
      "id": "64618",
      "name": "<installation name>",
      "config": { ... },
      "nav20": "<bool>",
      "nav20_online": 1,
      "navpro": "<bool>",
      "navpro_online": 0,
      "online": 0
    }
  ]
}

The fields nav20_online / navpro_online are cloud connectivity markers and not a literal Navigator generation — on a confirmed Navigator 10 installation nav20_online: 1 is set, apparently because cloud connectivity runs generically through that channel.

/api/installation/values – response structure

Top-level keys of the JSON response:

Key Type Meaning
mode string system mode (for example icon_12, icon_auto)
state string system status
sum_heat string total heat quantity, for example "31549.6 kWh" (with unit!)
temp_outside string outdoor temperature with unit
temp_heat string flow/return with unit
temp_hygienic string hygienic DHW temperature with unit
temp_water string DHW temperature with unit
temp_water_params dict {default, max, min, value} for the DHW setpoint
error string/int error count
errors list[...] error details
circuits list[dict] heating circuits (see below)
system_mode_params list available system modes
circuit_mode_params list available circuit modes
solar_mode_params list solar modes (where supported)
online, nav20_online, navpro_online int connectivity status

Per circuit (circuits[i]):

info, mode, sensor_hum, state, temp_forerun, temp_forerun_actual,
temp_params_eco, temp_params_normal, temp_room, temp_room_actual,
temp_room_value

Values typically arrive as strings with a unit suffix (for example "52.7 °C"), which the client has to strip.

Mode and state icon mappings

IDM encodes modes and states as icon class names (HTML/CSS strings), not as numeric values. The following table is the decoded assignment from ioBroker.idm and Beyer 2018:

System mode (mode)

Icon string Meaning
icon_12 off
icon_auto automatic
icon_3 domestic hot water / one-off DHW charge

System state (state)

Icon string Meaning
icon_12 off
icon_3 heating for DHW
icon_5 heating

Circuit mode (circuits[i].mode)

Icon string Meaning numeric (for /command)
icon_12 off 0
icon_24 time program 1
icon_21 normal 2
icon_11 eco 3
icon_10 manual heating 4
icon_1 manual cooling 5

System mode values for /api/installation/command (command=system_mode)

Value Meaning
0 off
1 automatic
2 domestic hot water
3 one-off domestic hot water (button character; jumps back to automatic)

Data freshness and consistency

The cloud data is 30–60 minutes old, because the heat pump only uploads to the cloud at that interval. A plausibility comparison against local Modbus reads (July 2026, Navigator 10 installation) confirms semantic consistency:

Cloud value Modbus source Difference
sum_heat: 31549.6 kWh total_heat_energy (register 4128) ~1 kWh (cloud is older)
temp_outside: 21.6 °C outdoor_temp (register 1000) typical daily curve
temp_hygienic: 59 °C dhw_temp_top (register 1014) ±1 K

What the legacy API does not offer

  • ❌ a firmware update endpoint — neither a trigger nor a status query
  • ❌ writing temperature setpoints (mode commands only)
  • ❌ solar, ISC, booster, cascade or zone data (base heating circuit only)
  • ❌ live data (30–60 min older than local)
  • ❌ authentication at a modern level (SHA1 without salt, possibly TLS chain problems)

New OAuth2 API (as of July 2026: not documented)

The current myIDM web frontend (app.myidm.at) uses a modern OAuth2+PKCE API under a.myidm.at/api/v1/. The old SHA1 API and the new OAuth2 API exist side by side, but the OAuth2 API has not been reverse-engineered yet.

Known paths of the v1 API (directory only, verified through a read-only GET on /api/v1/ after a Django session login):

/api/v1/heatpumps/
/api/v1/heatpumps/errors-log/
/api/v1/users/
/api/v1/translations/
/api/v1/texts/
/api/v1/errors/
/api/v1/bookmarks_new/
/api/v1/bookmarks/
/api/v1/channels/
/api/v1/data-act-channels/
/api/v1/virtual-channels/
... (list incomplete)

The endpoint list suggests a larger feature set than the legacy API (virtual-channels, data-act-channels), but the API requires an OAuth2 bearer token whose PKCE flow could not be fully reproduced in that session (the Django session was accepted, but the /api/v1/oauth2/authorize endpoint refuses to be reused for the SPA redirect).

Open for future research:

  • the complete PKCE flow with correct code_verifier handling
  • listing all /api/v1/... endpoints including write and update options
  • reverse-engineering the SPA app.myidm.at for API call patterns

Should the OAuth2 API be decoded in a future session, the documentation here should be extended.

Relation to the integration

This integration is deliberately 100 % local (Modbus + Nav 10 WS) and uses neither of the two cloud APIs. See the section "Deliberately not implemented". The cloud API documentation here serves completeness and support purposes only, as well as possible future features (an optional cloud fallback when Modbus detection fails, for example).

Code copied