IDM Heatpump Documentation
GitHub
Edit on GitHub

KNX Bridge

[!WARNING] Experimental. Automated behavior is covered by tests and static analysis. Setup, safe receive-only configuration and integration reload were also exercised on a live Home Assistant installation with an active KNX interface. No IDM group addresses had been imported into ETS, no physical group-address telegram was sent or decoded, and first-export bus load remains unmeasured. Treat it as something to try and report on, not as something to depend on. See docs/release-evidence/0.16.0-rc.6.md for exactly what is and is not verified.

Publish the heat pump on a KNX bus and take commands back from it — using the KNX integration Home Assistant already has, and without the IDM KNX gateway module.


What this replaces

IDM sells KNX connectivity for the Navigator as a Weinzierl KNX IP BAOS 774 module, configured in ETS with IDM's example project. That project defines a fixed set of communication objects: object 1 is the outdoor temperature, object 4 the system mode, object 222 the operating mode of heating circuit A, and so on — each with a datapoint type and a direction.

The KNX bridge recreates that object list from the Modbus values this integration already reads. A KNX installation sees the same object numbers, the same datapoint types and the same read/write directions as it would with the hardware module, so existing visualisations, room controllers and logic blocks keep working — the gateway is just gone.

The bridge is not a KNX stack. It calls the Home Assistant KNX integration for everything on the bus side. IP tunnelling, IP routing, the gateway connection and KNX Secure all come from there and are configured there. If the KNX integration is not set up, the bridge stays idle and raises a repair issue.


Requirements

Home Assistant KNX integration Set up and connected to a gateway or tunnel
IDM Heatpump integration Running over Modbus (a web-only entry has no register values to publish)
Free KNX main group The catalogue needs 1000 consecutive group addresses

Where it lives in the UI

The bridge is part of the integration's options, so it appears in two places and nowhere else:

Flow KNX bridge
Initial setup (adding the integration) Yes — after the main options step
Configure on an existing entry Yes — same step, prefilled with what is stored
Reconfigure menu No. That menu edits connection settings (host, port, slave ID) and runs diagnostics; it does not touch options at all, the same way room temperature forwarding and the web supplement are not there either.

Switching the bridge off keeps the configured base address, object groups and overrides, so turning it back on does not cost you the ETS mapping.

In web-only mode the bridge stays off regardless of the setting: it serves Modbus register values, which a web-only entry does not read. The log says so at startup.

Enabling it

  1. Settings → Devices & Services → IDM Heatpump → Configure
  2. Open the KNX bridge section and switch on Enable KNX bridge. The section also carries:
    • Send values to KNX — publish a telegram whenever a value changes
    • Accept commands from KNX — write incoming values into the heat pump
    • Answer read requests — reply to a GroupValueRead with the current value
    • Full resend interval — resend every value periodically (0 = only on change)
    • Change tolerance — how far a numeric value must move before it is sent again
  3. Submit. A KNX group addresses step follows with:
    • Base group address — see below
    • Object groups — which parts of the catalogue take part
    • Group address overrides — for objects your ETS project already addresses differently

How group addresses are assigned

IDM's example project ships with an empty group address table: every installation assigns its own. The bridge therefore derives them from one base address plus the IDM object number:

group address = base address + object number

With the default base 8/0/0:

IDM object Value Group address
1 Outdoor temperature 8/0/1
4 System mode 8/0/4
21 Hot water setpoint 8/0/21
222 Operating mode heating circuit A 8/0/222
400 Heat quantity heating 8/1/144
999 Total thermal energy 8/3/231

The whole catalogue fits inside one main group (8/0/1 … 8/3/231), so a single free main group is all the planning it needs.

Overrides

If your ETS project already uses different addresses, list the exceptions — one per line, register = address:

outdoor_temp = 1/2/3
system_mode = 1/2/4
# lines starting with a hash are ignored

An entry with an empty address excludes that object from the bridge entirely. Everything not listed keeps its derived address.


Object groups

Each catalogue entry belongs to one group, and only the selected groups are published and registered:

Group Contents
system Outdoor temperature, system mode, error number, buffer temperatures, error acknowledge
heat_pump Flow/return, heat source, compressors, pumps, bivalence points, faults
dhw Hot water temperatures and setpoint
heating_circuits Circuits A–G: flow, room, setpoints, curve, limits, modes, external room temperature
zones Zone modules 1–10 with up to 8 rooms each
glt Building-management inputs: external temperatures, humidity, demand requests
energy Heat quantities and current power
solar Collector, return, charging temperatures and solar mode
isc ISC cooling temperatures and mode
cascade Available/running stages, requested temperatures, power and bivalence limits
booster Booster 1 and 2 temperatures, pumps, compressors
pv PV, battery, house consumption, total electric and thermal output

Objects whose register the connected controller does not expose are skipped automatically, so a Navigator without a zone module never puts zone objects on the bus.


Direction

Every object carries the direction IDM gave it in the example project:

  • Read-only objects (temperatures, states, energy counters) are published only. A telegram arriving on one of them is ignored.
  • Writable objects (modes, setpoints, external temperatures, demand requests) are published and registered for incoming telegrams. A group write on such an address is written into the corresponding Modbus register through the normal write path, including its safety checks, write cooldown and EEPROM protection.

KNX controls can emit intermediate values while a dial is turned or an arrow is tapped. The bridge therefore keeps the newest value per register for a one-second quiet period and writes only that final value. If the normal write cooldown or the EEPROM interval is still active, the newest value stays queued and is applied after the guard expires; a later telegram replaces it. Values that already match the current coordinator state do not consume a write cycle.

This changes command handling, not write safety. The EEPROM-sensitive register classification and the default 60-second EEPROM interval are unchanged. The interval remains configurable in the integration settings for owners who deliberately accept a different wear-versus-latency trade-off.

Read requests

A KNX device that asks for a value — a push-button refreshing its display after a restart, a visualisation coming back up — sends a GroupValueRead. The bridge answers it with the value the heat pump currently reads, as a GroupValueResponse, which is what the BAOS gateway does too.

The reply goes out immediately rather than through the paced send queue: a read request is answered now or not usefully at all, and the number of them is bounded by the devices asking. Write-only objects and values the controller reports as unused are not answered, because there is nothing to answer with.

Switching Answer read requests off leaves those addresses unregistered and the bridge silent on reads. A GroupValueResponse from another device is never written into the heat pump: it answers somebody else's question rather than instructing us.

Incoming registration goes through the KNX integration's knx.event_register service, so no change to the KNX integration's own event filter is needed.

Two guards keep the bus and the controller from talking in circles: only telegrams marked as incoming are acted upon, and a value that merely echoes what the bridge published moments earlier is not written back.


Ready-made ETS import files

The bridge sends on the group addresses, but ETS still needs them to exist in the project so the real KNX devices — a push-button showing the flow temperature, a visualisation, a logic module — can be linked to them. Two generated files are in the repository so nobody types several hundred addresses by hand:

File Contents
idm-waermepumpe-kompakt.xml 43 addresses: what a display or visualisation realistically shows, plus the values a KNX installation can feed back into the heat pump. Heating circuits A and B.
idm-waermepumpe-komplett.xml all 654 objects

Both assume the default base address 8/0/0. The matching .csv files are a readable reference — object number, register, direction — not import files.

Import into ETS 6 (three-level group address style): back the project up, right-click the top entry under Group Addresses, choose Import Group Addresses, pick the .xml, then check the import report against addresses that already exist.

Generating your own

If 8/0/0 is taken in your project, or you want a different selection, the easiest way is the group address generator on the documentation website: enter your base address, pick a preset or object groups, download the .xml. The command-line generator does the same from a checkout of this repository:

# A curated subset on main group 11
python scripts/generate_knx_group_addresses.py --base 11/0/0 --profile compact --output ./out

# Only what a visualisation needs
python scripts/generate_knx_group_addresses.py --base 11/0/0 --groups system,dhw,energy --output ./out

# Named registers, whatever you like
python scripts/generate_knx_group_addresses.py --base 11/0/0 \
  --registers outdoor_temp,dhw_setpoint,hc_a_mode --output ./out

The names come from the integration's own German name table, so an address reads in ETS the way the matching entity reads in Home Assistant.

Exporting the object list for ETS

The idm_heatpump.export_knx_group_addresses action answers with the table for this controller — object number, group address, datapoint type, direction and unit — so a fresh ETS project can be built from it:

action: idm_heatpump.export_knx_group_addresses
target:
  entity_id: sensor.idm_heatpump_outdoor_temperature
data:
  knx_base_address: "8/0/0"
response_variable: knx_objects

The response looks like this:

base_address: "8/0/0"
count: 187
objects:
  - object: 1
    group_address: "8/0/1"
    register: outdoor_temp
    dpt: "9.001"
    group: system
    writable: false
    unit: "°C"

Both fields are optional: without them the action uses the addresses and object groups configured for the bridge.


Bus load

A first export sends one telegram per object, so the bridge paces them at about 20 telegrams per second and only sends a value again once it has actually moved further than the configured tolerance. On a plant with many heating circuits and zone modules, restrict the object groups to what the KNX side really consumes rather than publishing all of them.


Datapoint types

The catalogue uses IDM's own datapoint types where the example project states one, and derives the rest from the register:

Kind of value DPT
Temperatures 9.001
Humidity 9.007
Power (kW) 9.024
Heat quantities (kWh) 14.031
Percentages 5.001
Modes, states, counters 7.001 (5.010 for the system mode)
Bivalence points (signed °C) 8.001
Demand requests 1-bit, sent as a raw 0/1 payload

Troubleshooting

Repair issue "KNX bridge inactive" The KNX integration is not set up. Add it first, then reload the IDM Heatpump entry.

Nothing arrives on the bus Check that Send values to KNX is on, that the object's group is selected, and that the controller actually reports the value — objects whose register is missing or marked unused are skipped.

A push-button stays blank after a restart Check that Answer read requests is on. If the device does not send a read request at all, set a Full resend interval so every value is repeated periodically.

A command from KNX has no effect Only objects IDM marks as writable accept commands. Check that Accept commands from KNX is on, and look for a write error in the log: the write goes through the same safety checks as any other write. A value outside the register range is rejected. An active general or EEPROM cooldown keeps the newest valid command queued and applies it when the guard expires.

Two objects share an address The override list refuses a duplicate address, and it also refuses an override that claims the derived address of another served object — one of the two would silently shadow the other. If the derived addresses collide with something else on the bus, move the base address to a free main group.


Not covered

Two objects from the example project are deliberately absent: the external pump demand objects 384 (brine / intermediate pump) and 385 (groundwater pump). IDM's own labels do not map unambiguously onto the two corresponding registers, and a wrong guess would command the wrong pump. Use the write_register action for those until the mapping is confirmed on hardware.


See also: Configuration · Services · Modbus registers