Example Automations

Here you'll find practical examples for using the IDM Heatpump integration, especially how to write values via automations.


Writing Values via Automation (Overview)

In Home Assistant, writable values of the heat pump are represented as entities. To change these values in automations, you don't use idm_heatpump.write_register, but the standard Home Assistant services:

  • For temperatures, heating curves, or setpoints (type number): service number.set_value
  • For operating modes (type select): service select.select_option
  • For switches (type switch): service switch.turn_on or switch.turn_off

Alternative (advanced): If a register doesn't exist as an entity, you can use the idm_heatpump.write_register service (see Services Reference).

Here are some concrete use cases:


Auto-activate holiday mode

Switches the heat pump to holiday mode when you leave the house:

automation:
  - alias: "Heat pump: Holiday mode when away"
    trigger:
      - platform: state
        entity_id: person.me
        to: "not_home"
        for:
          hours: 2
    action:
      - service: idm_heatpump.set_system_mode
        data:
          mode: "holiday"

Normal operation on return

automation:
  - alias: "Heat pump: Auto mode on return"
    trigger:
      - platform: state
        entity_id: person.me
        to: "home"
    action:
      - service: idm_heatpump.set_system_mode
        data:
          mode: "automatic"

Fault notification

Sends a push notification when a fault occurs:

automation:
  - alias: "Heat pump: Fault notification"
    trigger:
      - platform: state
        entity_id: binary_sensor.idm_heatpump_fault
        to: "on"
    action:
      - service: notify.mobile_app
        data:
          title: "⚠️ Heat Pump Fault"
          message: >
            IDM fault active. Error code: {{ states('sensor.idm_heatpump_error_code') }}

Forward energy-management measurements through the GLT service

The set_external_power action forwards any available subset of PV, house and battery measurements without depending on generated number entities. The integration keeps datatype, register-availability and write-safety checks in the write path. Replace the example sensor IDs with your actual IDs. Do not run this automation if an inverter, E3DC, Smartfox or another controller already writes the same registers.

automation:
  - alias: "Heat pump: Forward external power measurements"
    mode: restart
    trigger:
      - platform: state
        entity_id: sensor.house_pv_surplus_kw
    action:
      - action: idm_heatpump.set_external_power
        data:
          pv_surplus: "{{ states('sensor.house_pv_surplus_kw') }}"
          pv_production: "{{ states('sensor.house_pv_production_kw') }}"
          house_consumption: "{{ states('sensor.house_consumption_kw') }}"

Invalid, unavailable, NaN or infinite inputs are rejected by the action. If a source sensor can be unavailable independently, either omit that field in a separate call or build the action data dynamically rather than replacing it with zero. Multiple fields are validated before writing, but their individual Modbus writes are not atomic; the next cyclic update should resend the complete current set after a connection failure. See Services Reference.

Thresholds at which a heat pump starts, stops or modulates depend on the exact model, firmware, temperatures and controller configuration. A fixed 2–3 kW threshold is therefore not a universal default.


Request DHW charging with explicit safety stops

For a temporary external request, prefer the generated switch for register 1712 over repeatedly changing an EEPROM-backed DHW setpoint. The thresholds below are examples only and must be agreed with the installer for the actual hydraulic system.

automation:
  - alias: "Heat pump: Start DHW request from PV"
    trigger:
      - platform: numeric_state
        entity_id: sensor.house_pv_surplus_kw
        above: 3.0
        for:
          minutes: 10
    condition:
      - condition: numeric_state
        entity_id: sensor.idm_heatpump_dhw_temp_bottom
        below: 50
    action:
      - service: switch.turn_on
        target:
          entity_id: switch.idm_heatpump_demand_dhw_charging

  - alias: "Heat pump: Stop external DHW request"
    mode: restart
    trigger:
      - platform: numeric_state
        entity_id: sensor.idm_heatpump_dhw_temp_bottom
        above: 54
      - platform: numeric_state
        entity_id: sensor.house_pv_surplus_kw
        below: 0.5
        for:
          minutes: 10
      - platform: state
        entity_id: switch.idm_heatpump_demand_dhw_charging
        to: "on"
        for:
          minutes: 60
    action:
      - service: switch.turn_off
        target:
          entity_id: switch.idm_heatpump_demand_dhw_charging

External requests should always have temperature, low-surplus and maximum-time stop paths. Verify the behavior with the Navigator GLT Monitor before leaving the automation unattended.


PV surplus operation as a state (forecast helper)

The derived diagnostic PV-Überschussbetrieb (binary_sensor.<device>_pv_uberschussbetrieb; see Entities → PV / Energy Management → PV surplus operation) is on while surplus is signalled to the controller and the heat pump is drawing electrical power. It replaces hand-written template logic that combines PV and grid sensors, e.g. for energy-forecast helpers:

template:
  - sensor:
      - name: "Heat pump PV surplus consumption"
        unit_of_measurement: "kW"
        state: >-
          {% if is_state('binary_sensor.idm_heatpump_pv_uberschussbetrieb', 'on') %}
            {{ states('sensor.idm_heatpump_power_consumption_hp') | float(0) }}
          {% else %}
            0
          {% endif %}

On installations where pv_surplus is measured behind the heat pump feeder and collapses toward zero while charging, feed the SG-Ready Supergreen signal into the heat pump (or rely on the smart_grid_status source the diagnostic already evaluates) instead of the shrinking surplus value.


EEPROM-backed DHW setpoint boost (use sparingly)

This alternative changes a persistent setpoint. It is suitable only for occasional mode changes, not rapid tracking of fluctuating PV power:

automation:
  - alias: "Heat pump: DHW boost on PV surplus"
    trigger:
      - platform: numeric_state
        entity_id: sensor.idm_heatpump_pv_surplus
        above: 2.0
        for:
          minutes: 15
    action:
      - service: number.set_value
        target:
          entity_id: number.idm_heatpump_dhw_setpoint
        data:
          value: 60
  - alias: "Heat pump: End DHW boost"
    trigger:
      - platform: numeric_state
        entity_id: sensor.idm_heatpump_pv_surplus
        below: 0.5
        for:
          minutes: 10
    action:
      - service: number.set_value
        target:
          entity_id: number.idm_heatpump_dhw_setpoint
        data:
          value: 48

Heating circuit mode by schedule

Switches heating circuit A daily on a schedule:

automation:
  - alias: "Heat pump: Circuit A – Schedule"
    trigger:
      - platform: time
        at: "22:00:00"
    action:
      - service: select.select_option
        target:
          entity_id: select.idm_heatpump_circuit_a_mode
        data:
          option: "Eco"
  - alias: "Heat pump: Circuit A – Normal operation"
    trigger:
      - platform: time
        at: "06:00:00"
    action:
      - service: select.select_option
        target:
          entity_id: select.idm_heatpump_circuit_a_mode
        data:
          option: "Normal"

Energy Dashboard

Use native IDM energy sensors when your device exposes them with stable values. Where the device only exposes power, use Home Assistant helpers to integrate power over time instead of treating a power sensor as a native energy meter.

# Daily heating energy (in configuration.yaml or helpers)
sensor:
  - platform: integration
    source: sensor.idm_heatpump_current_heating_power
    name: Daily energy heating
    unit_prefix: k
    round: 2

For dashboard cards, prefer sensors with kWh and total_increasing semantics. If a model does not expose a reliable total energy register, create an HA integration helper and name it clearly as a calculated value.


Smart Grid Control

Reacts to the heat pump's Smart Grid status:

automation:
  - alias: "SmartGrid: Read heat pump status"
    trigger:
      - platform: state
        entity_id: sensor.idm_heatpump_smart_grid_status
    action:
      - service: notify.persistent_notification
        data:
          title: "Smart Grid Status"
          message: "Current Smart Grid status: {{ states('sensor.idm_heatpump_smart_grid_status') }}"

Temporary Load Limitation

Power limit registers are model-dependent and disabled by default. Only enable and automate them after confirming support for your exact model and firmware.

automation:
  - alias: "Heat pump: temporary power limit"
    trigger:
      - platform: state
        entity_id: binary_sensor.grid_limit_active
        to: "on"
    action:
      - service: number.set_value
        target:
          entity_id: number.idm_heatpump_power_limit_hp
        data:
          value: 3.5
  - alias: "Heat pump: clear temporary power limit"
    trigger:
      - platform: state
        entity_id: binary_sensor.grid_limit_active
        to: "off"
    action:
      - service: number.set_value
        target:
          entity_id: number.idm_heatpump_power_limit_hp
        data:
          value: -1

Acknowledge errors (manually via button helper)

# button-helper in configuration.yaml
button:
  - platform: template
    buttons:
      idm_acknowledge_errors:
        friendly_name: "Acknowledge IDM faults"
        press:
          service: idm_heatpump.acknowledge_errors
Code copied