Modbus Registers

Overview

The integration does not poll one fixed list. idm-heatpump-api builds a register map from the detected Navigator family, active heating circuits, zone modules/rooms and optional Solar, ISC, PV and cascade capabilities. This keeps unsupported feature blocks out of normal polls.

The authoritative machine-readable register schema is generated by idm-heatpump-api. Its schema snapshot includes each register's address, datatype, access flags, write class, source, source version, supported models, sentinel values and optional verification label.

→ Open the complete register catalog

Address Ranges

Range Addresses Description
PV/Battery 74-86 Photovoltaics and battery
System 1000-1199 System parameters, temperatures, pressures
Cascade/Bivalence 1200-1349 Multi-HP, heating element
Heating Circuits A-G 1350-1699 Individual heating circuits
BMS/Energy 1700-1799 Remote maintenance, energy measurement
Zones 1-10 2000-2999 Zone modules with room control

Data Types

Type Description
FLOAT IEEE 754 floating point (2 Modbus words, low word first)
UCHAR 8-bit unsigned value in one Modbus word
INT8 8-bit signed value
UINT16 16-bit unsigned value
INT16 16-bit signed value
BOOL Boolean 0/1
BITFLAG Bit field decoded to active flags

Important: When writing integer values (UCHAR, INT8, INT16, UINT16), the integration automatically applies the multiplier stored in the code and rounds the value accordingly.

Modbus Parameters

Parameter Value
Protocol Modbus TCP
Default Port 502
Slave ID 1
FC Read input 04 (Read Input Registers)
FC Read holding 03 (Read Holding Registers)
FC Write 16 (Write Multiple Registers)

Zone Base Addresses

Zone Base Address
Zone 1 2000
Zone 2 2065
Zone 3 2130
Zone 4 2195
Zone 5 2260
Zone 6 2325
Zone 7 2390
Zone 8 2455
Zone 9 2520
Zone 10 2585

Each module is 65 addresses apart. A room occupies seven addresses beginning at base + 2; up to eight rooms can be configured, while six is the current Navigator 10 default.

Special Registers

Address Description Special Note
1999 Error acknowledgment Must NOT be written permanently
1696 BMS heat request Must be written cyclically every 10 min
1698 BMS cooling request Must be written cyclically every 10 min

EEPROM-sensitive Registers

88 registers are EEPROM-sensitive and have a limited number of write cycles. The integration automatically warns about frequent writing of these registers.

Register Quality Rules

  • New registers must come from the API register schema, not from ad-hoc Home Assistant code.
  • Model-specific registers must be gated by detected model capabilities before polling.
  • Sentinel values are interpreted contextually; documented enum values take precedence over generic unavailable sentinels.
  • Real-device deviations are tracked as compatibility notes and regression tests before being advertised as supported features.
  • Batches contain only exactly adjacent, non-overlapping logical ranges and are limited to 40 Modbus words.
  • A custom raw write can validate encoding but cannot infer safe ranges, EEPROM behavior or meaning for an unknown address.

External energy-manager ownership

Some GLT/PV input registers are designed to be supplied continuously by an external energy manager. For example, official iDM documentation defines register 74 as the writable current PV surplus and register 4122 as the read-only current heat-pump power consumption. If an inverter, E3DC, Smartfox or another controller already writes a GLT/PV value, a Home Assistant write can only override it until that controller's next communication cycle.

Avoid multiple writers for the same register. Before creating an automation, identify which system owns the value and use the register's library metadata for datatype, write class, range and cyclic behavior. Do not infer semantics from an address used by a different installation or firmware; for example, this integration maps Smart Grid status and the configurable variable input as separate registers.

PV/energy-management datatype reference

The addresses in the PV block do not all share the same datatype. In particular, battery SOC must not be encoded as a two-register float.

Address Entity Datatype Unit Notes
74 pv_surplus FLOAT, word-swapped kW Writable GLT input; not EEPROM
76 electric_heater_power FLOAT, word-swapped kW Writable GLT measurement
78 pv_production FLOAT, word-swapped kW Writable GLT measurement
82 house_consumption FLOAT, word-swapped kW Writable GLT measurement
84 battery_discharge FLOAT, word-swapped kW Writable GLT measurement
86 battery_soc signed INT16, one register % 0–100; -1 means unavailable
88 pv_target_value FLOAT, word-swapped kW Model/firmware dependent

Always use the generated entity or library register definition when writing. The advanced raw-write action cannot infer the correct datatype from an address.

Complete register catalog

Generated from idm-heatpump-api[web]==2.6.0. Do not edit this section manually.

This maximal catalog contains 687 logical register definitions: all heating circuits A–G, ten zone modules with eight rooms each, and Solar, ISC, PV, cascade and Navigator 10 extensions. The integration selects only the subset supported and enabled on the detected installation.

Of these definitions, 451 are writable, 88 are EEPROM-sensitive and 2 require cyclic writes. FLOAT values occupy two Modbus words; the table therefore shows an address range for them. R means read-only, RW read/write and W write-only.

The German description is intended for identification; the code-form register name is the authoritative key used by the integration. Availability can vary by Navigator model and firmware.

74–999 · PV & Smart Grid (8)

Address(es) Description (DE) Register name Type Unit Access Note
74–75 PV Überschuss pv_surplus FLOAT kW RW —
76–77 E-Heizstab Leistung electric_heater_power FLOAT kW RW —
78–79 PV Produktion pv_production FLOAT kW RW —
82–83 Hausverbrauch house_consumption FLOAT kW RW —
84–85 Batterie Entladung battery_discharge FLOAT kW RW —
86 Batterie SOC battery_soc INT16 % RW —
88–89 PV Zielwert pv_target_value FLOAT kW RW —
90 Smart Grid Status smart_grid_status UCHAR — R Enum

1000–1199 · System & heat pump (64)

Address(es) Description (DE) Register name Type Unit Access Note
1000–1001 Außentemperatur outdoor_temp FLOAT °C R —
1002–1003 Gemittelte Außentemperatur outdoor_temp_avg FLOAT °C R —
1004 Interne Meldung internal_message UINT16 — R —
1005 Systembetriebsart system_mode UCHAR — RW · EEPROM Enum
1006 Variabler Eingang variable_input UCHAR — R Enum
1008–1009 Wärmespeichertemperatur storage_temp FLOAT °C R —
1010–1011 Kältespeichertemperatur cold_storage_temp FLOAT °C R —
1012–1013 Trinkwassererwärmer unten dhw_temp_bottom FLOAT °C R —
1014–1015 Trinkwassererwärmer oben dhw_temp_top FLOAT °C R —
1030–1031 Warmwasser Zapftemperatur dhw_tapping_temp FLOAT °C R —
1032 Warmwasser Sollwert dhw_setpoint UCHAR °C RW · EEPROM —
1033 WW Einchargetemperatur dhw_charge_on_temp UCHAR °C RW · EEPROM —
1034 WW Ausschalttemperatur dhw_charge_off_temp UCHAR °C RW · EEPROM —
1048–1049 Aktueller Strompreis current_electricity_price FLOAT €/MWh R —
1050–1051 Wärmepumpen Vorlauftemperatur hp_flow_temp FLOAT °C R —
1052–1053 Wärmepumpen Rücklauftemperatur hp_return_temp FLOAT °C R —
1054–1055 HGL Vorlauftemperatur B35 hgl_flow_temp FLOAT °C R —
1056–1057 Wärmequelleneintritt heat_source_inlet_temp FLOAT °C R —
1058–1059 Wärmequellenaustritt heat_source_outlet_temp FLOAT °C R —
1060–1061 Luftansaugtemperatur air_intake_temp FLOAT °C R —
1062–1063 Luftwärmetauscher Temperatur air_heat_exchanger_temp FLOAT °C R —
1064–1065 Luftansaugtemperatur 2 air_intake_temp_2 FLOAT °C R —
1066–1067 Ladefühler Temperatur charging_sensor_temp FLOAT °C R —
1068–1069 Rücklauftemperatur Wärmesenke heat_sink_return_temp FLOAT °C R Navigator 10
1070–1071 Vorlauftemperatur Wärmesenke heat_sink_flow_temp FLOAT °C R Navigator 10
1072 Durchfluss Wärmesenke (B2) heat_sink_flow_rate UCHAR L/min R Navigator 10
1074 Ladepumpe Wärmesenke heat_sink_charging_pump_signal INT16 % R Navigator 10
1086–1087 Grundwassereintrittstemperatur 1 groundwater_inlet_temp_1 FLOAT °C R Navigator 10
1088–1089 Grundwassereintrittstemperatur 2 groundwater_inlet_temp_2 FLOAT °C R Navigator 10
1090 Wärmepumpen Betriebsart hp_operating_mode UCHAR — R Enum
1091 Heizanforderung heating_demand UCHAR — R Binary
1092 Kühlanforderung cooling_demand UCHAR — R Binary
1093 Warmwasseranforderung dhw_demand UCHAR — R Binary
1098 EVU Sperre evu_lock UCHAR — R Enum
1099 Summenstörung hp_sum_alarm UCHAR — R Binary
1100 Verdichter 1 compressor_status_1 UCHAR — R Binary
1101 Verdichter 2 compressor_status_2 UCHAR — R Binary
1102 Verdichter 3 compressor_status_3 UCHAR — R Binary
1103 Verdichter 4 compressor_status_4 UCHAR — R Binary
1104 Ladepumpe M73 charging_pump_status INT16 % R —
1105 Sole-/Zwischenkreispumpe brine_pump_status INT16 % R —
1106 Wärmequellenpumpe M15 heat_source_pump_status INT16 % R —
1108 ISC Kältespeicherpumpe M84 isc_cold_storage_pump_status INT16 % R —
1109 ISC Rückkühlpumpe M17 isc_recooling_pump_status INT16 % R —
1110 Umschaltventil Heizkreis Heizen/Kühlen valve_hc_heat_cool UINT16 — R —
1111 Umschaltventil Speicher Heizen/Kühlen valve_storage_heat_cool UINT16 — R —
1112 Umschaltventil Heizen/Warmwasser valve_heat_dhw UINT16 — R —
1113 Wärmequelle Umschaltventil valve_heat_source_heat_cool UINT16 — R —
1114 Solar Umschaltventil Heizen/WW valve_solar_heat_dhw UINT16 — R —
1115 Solar Speicher/Wärmequelle Ventil valve_solar_storage_heat_source UINT16 — R —
1116 ISC Umschaltventil valve_isc_heat_source_cold_storage UINT16 — R —
1117 Umschaltventil ISC Speicher/Bypass valve_isc_storage_bypass UINT16 — R —
1118 Zirkulationspumpe M64 circulation_pump UINT16 — R —
1120 Bivalenzpunkt 1 (2. WE) bivalence_point_1_2nd_gen INT16 °C RW · EEPROM —
1121 Bivalenzpunkt 2 (2. WE) bivalence_point_2_2nd_gen INT16 °C RW · EEPROM —
1122 Bivalenzpunkt 1 (3. WE) bivalence_point_1_3rd_gen INT16 °C RW · EEPROM —
1123 Bivalenzpunkt 2 (3. WE) bivalence_point_2_3rd_gen INT16 °C RW · EEPROM —
1124 Bivalenz Betriebszustand bivalence_state UCHAR — R Enum
1147 Kaskade verfügbar Heizen cascade_available_heating UCHAR — R —
1148 Kaskade verfügbar Kühlen cascade_available_cooling UCHAR — R —
1149 Kaskade verfügbar Warmwasser cascade_available_dhw UCHAR — R —
1150 Kaskade in Betrieb Heizen cascade_running_heating UCHAR — R —
1151 Kaskade in Betrieb Kühlen cascade_running_cooling UCHAR — R —
1152 Kaskade in Betrieb Warmwasser cascade_running_dhw UCHAR — R —

1200–1349 · Cascade & bivalence (18)

Address(es) Description (DE) Register name Type Unit Access Note
1200–1201 Kaskade Angeforderte Heiztemperatur cascade_req_heating_temp FLOAT °C R —
1202–1203 Kaskade Angeforderte Kühltemperatur cascade_req_cooling_temp FLOAT °C R —
1204–1205 Kaskade Angeforderte WW-Temperatur cascade_req_dhw_temp FLOAT °C R —
1206–1207 Kaskade Gemittelte VL-Temp Heizen cascade_avg_flow_heating FLOAT °C R —
1208–1209 Kaskade Gemittelte VL-Temp Kühlen cascade_avg_flow_cooling FLOAT °C R —
1210–1211 Kaskade Gemittelte VL-Temp Warmwasser cascade_avg_flow_dhw FLOAT °C R —
1220 Kaskade Mindestleistung Heizen cascade_min_power_heating UCHAR % RW —
1221 Kaskade Maximalleistung Heizen cascade_max_power_heating UCHAR % RW —
1222 Kaskade Mindestleistung Kühlen cascade_min_power_cooling UCHAR % RW —
1223 Kaskade Maximalleistung Kühlen cascade_max_power_cooling UCHAR % RW —
1224 Kaskade Mindestleistung Warmwasser cascade_min_power_dhw UCHAR % RW —
1225 Kaskade Maximalleistung Warmwasser cascade_max_power_dhw UCHAR % RW —
1226 Kaskade Bivalenz Heizen Parallel cascade_bivalence_heating_parallel INT16 °C RW —
1227 Kaskade Bivalenz Heizen Alternativ cascade_bivalence_heating_alternative INT16 °C RW —
1228 Kaskade Bivalenz Kühlen Parallel cascade_bivalence_cooling_parallel INT16 °C RW —
1229 Kaskade Bivalenz Kühlen Alternativ cascade_bivalence_cooling_alternative INT16 °C RW —
1230 Kaskade Bivalenz WW Parallel cascade_bivalence_dhw_parallel INT16 °C RW —
1231 Kaskade Bivalenz WW Alternativ cascade_bivalence_dhw_alternative INT16 °C RW —

1350–1699 · Heating circuits & demands (123)

Address(es) Description (DE) Register name Type Unit Access Note
1350–1351 Vorlauftemperatur HK A hc_a_flow_temp FLOAT °C R —
1352–1353 Vorlauftemperatur HK B hc_b_flow_temp FLOAT °C R —
1354–1355 Vorlauftemperatur HK C hc_c_flow_temp FLOAT °C R —
1356–1357 Vorlauftemperatur HK D hc_d_flow_temp FLOAT °C R —
1358–1359 Vorlauftemperatur HK E hc_e_flow_temp FLOAT °C R —
1360–1361 Vorlauftemperatur HK F hc_f_flow_temp FLOAT °C R —
1362–1363 Vorlauftemperatur HK G hc_g_flow_temp FLOAT °C R —
1364–1365 Raumtemperatur HK A hc_a_room_temp FLOAT °C R —
1366–1367 Raumtemperatur HK B hc_b_room_temp FLOAT °C R —
1368–1369 Raumtemperatur HK C hc_c_room_temp FLOAT °C R —
1370–1371 Raumtemperatur HK D hc_d_room_temp FLOAT °C R —
1372–1373 Raumtemperatur HK E hc_e_room_temp FLOAT °C R —
1374–1375 Raumtemperatur HK F hc_f_room_temp FLOAT °C R —
1376–1377 Raumtemperatur HK G hc_g_room_temp FLOAT °C R —
1378–1379 Sollvorlauftemperatur HK A hc_a_setpoint_flow_temp FLOAT °C R —
1380–1381 Sollvorlauftemperatur HK B hc_b_setpoint_flow_temp FLOAT °C R —
1382–1383 Sollvorlauftemperatur HK C hc_c_setpoint_flow_temp FLOAT °C R —
1384–1385 Sollvorlauftemperatur HK D hc_d_setpoint_flow_temp FLOAT °C R —
1386–1387 Sollvorlauftemperatur HK E hc_e_setpoint_flow_temp FLOAT °C R —
1388–1389 Sollvorlauftemperatur HK F hc_f_setpoint_flow_temp FLOAT °C R —
1390–1391 Sollvorlauftemperatur HK G hc_g_setpoint_flow_temp FLOAT °C R —
1392–1393 Feuchtesensor humidity_sensor FLOAT % R —
1393 Betriebsart HK A hc_a_mode UCHAR — RW · EEPROM Enum
1394 Betriebsart HK B hc_b_mode UCHAR — RW · EEPROM Enum
1395 Betriebsart HK C hc_c_mode UCHAR — RW · EEPROM Enum
1396 Betriebsart HK D hc_d_mode UCHAR — RW · EEPROM Enum
1397 Betriebsart HK E hc_e_mode UCHAR — RW · EEPROM Enum
1398 Betriebsart HK F hc_f_mode UCHAR — RW · EEPROM Enum
1399 Betriebsart HK G hc_g_mode UCHAR — RW · EEPROM Enum
1401–1402 Raumsoll Heizen Normal HK A hc_a_room_setpoint_heat_normal FLOAT °C RW · EEPROM —
1403–1404 Raumsoll Heizen Normal HK B hc_b_room_setpoint_heat_normal FLOAT °C RW · EEPROM —
1405–1406 Raumsoll Heizen Normal HK C hc_c_room_setpoint_heat_normal FLOAT °C RW · EEPROM —
1407–1408 Raumsoll Heizen Normal HK D hc_d_room_setpoint_heat_normal FLOAT °C RW · EEPROM —
1409–1410 Raumsoll Heizen Normal HK E hc_e_room_setpoint_heat_normal FLOAT °C RW · EEPROM —
1411–1412 Raumsoll Heizen Normal HK F hc_f_room_setpoint_heat_normal FLOAT °C RW · EEPROM —
1413–1414 Raumsoll Heizen Normal HK G hc_g_room_setpoint_heat_normal FLOAT °C RW · EEPROM —
1415–1416 Raumsoll Heizen Eco HK A hc_a_room_setpoint_heat_eco FLOAT °C RW · EEPROM —
1417–1418 Raumsoll Heizen Eco HK B hc_b_room_setpoint_heat_eco FLOAT °C RW · EEPROM —
1419–1420 Raumsoll Heizen Eco HK C hc_c_room_setpoint_heat_eco FLOAT °C RW · EEPROM —
1421–1422 Raumsoll Heizen Eco HK D hc_d_room_setpoint_heat_eco FLOAT °C RW · EEPROM —
1423–1424 Raumsoll Heizen Eco HK E hc_e_room_setpoint_heat_eco FLOAT °C RW · EEPROM —
1425–1426 Raumsoll Heizen Eco HK F hc_f_room_setpoint_heat_eco FLOAT °C RW · EEPROM —
1427–1428 Raumsoll Heizen Eco HK G hc_g_room_setpoint_heat_eco FLOAT °C RW · EEPROM —
1429–1430 Heizkurve HK A hc_a_heating_curve FLOAT — RW · EEPROM —
1431–1432 Heizkurve HK B hc_b_heating_curve FLOAT — RW · EEPROM —
1433–1434 Heizkurve HK C hc_c_heating_curve FLOAT — RW · EEPROM —
1435–1436 Heizkurve HK D hc_d_heating_curve FLOAT — RW · EEPROM —
1437–1438 Heizkurve HK E hc_e_heating_curve FLOAT — RW · EEPROM —
1439–1440 Heizkurve HK F hc_f_heating_curve FLOAT — RW · EEPROM —
1441–1442 Heizkurve HK G hc_g_heating_curve FLOAT — RW · EEPROM —
1442 Heizgrenze HK A hc_a_heating_limit UCHAR °C RW · EEPROM —
1443 Heizgrenze HK B hc_b_heating_limit UCHAR °C RW · EEPROM —
1444 Heizgrenze HK C hc_c_heating_limit UCHAR °C RW · EEPROM —
1445 Heizgrenze HK D hc_d_heating_limit UCHAR °C RW · EEPROM —
1446 Heizgrenze HK E hc_e_heating_limit UCHAR °C RW · EEPROM —
1447 Heizgrenze HK F hc_f_heating_limit UCHAR °C RW · EEPROM —
1448 Heizgrenze HK G hc_g_heating_limit UCHAR °C RW · EEPROM —
1449 Festwertvorlauf HK A hc_a_setpoint_flow_constant UCHAR °C RW · EEPROM —
1450 Festwertvorlauf HK B hc_b_setpoint_flow_constant UCHAR °C RW · EEPROM —
1451 Festwertvorlauf HK C hc_c_setpoint_flow_constant UCHAR °C RW · EEPROM —
1452 Festwertvorlauf HK D hc_d_setpoint_flow_constant UCHAR °C RW · EEPROM —
1453 Festwertvorlauf HK E hc_e_setpoint_flow_constant UCHAR °C RW · EEPROM —
1454 Festwertvorlauf HK F hc_f_setpoint_flow_constant UCHAR °C RW · EEPROM —
1455 Festwertvorlauf HK G hc_g_setpoint_flow_constant UCHAR °C RW · EEPROM —
1457–1458 Raumsoll Kühlen Normal HK A hc_a_room_setpoint_cool_normal FLOAT °C RW · EEPROM —
1459–1460 Raumsoll Kühlen Normal HK B hc_b_room_setpoint_cool_normal FLOAT °C RW · EEPROM —
1461–1462 Raumsoll Kühlen Normal HK C hc_c_room_setpoint_cool_normal FLOAT °C RW · EEPROM —
1463–1464 Raumsoll Kühlen Normal HK D hc_d_room_setpoint_cool_normal FLOAT °C RW · EEPROM —
1465–1466 Raumsoll Kühlen Normal HK E hc_e_room_setpoint_cool_normal FLOAT °C RW · EEPROM —
1467–1468 Raumsoll Kühlen Normal HK F hc_f_room_setpoint_cool_normal FLOAT °C RW · EEPROM —
1469–1470 Raumsoll Kühlen Normal HK G hc_g_room_setpoint_cool_normal FLOAT °C RW · EEPROM —
1471–1472 Raumsoll Kühlen Eco HK A hc_a_room_setpoint_cool_eco FLOAT °C RW · EEPROM —
1473–1474 Raumsoll Kühlen Eco HK B hc_b_room_setpoint_cool_eco FLOAT °C RW · EEPROM —
1475–1476 Raumsoll Kühlen Eco HK C hc_c_room_setpoint_cool_eco FLOAT °C RW · EEPROM —
1477–1478 Raumsoll Kühlen Eco HK D hc_d_room_setpoint_cool_eco FLOAT °C RW · EEPROM —
1479–1480 Raumsoll Kühlen Eco HK E hc_e_room_setpoint_cool_eco FLOAT °C RW · EEPROM —
1481–1482 Raumsoll Kühlen Eco HK F hc_f_room_setpoint_cool_eco FLOAT °C RW · EEPROM —
1483–1484 Raumsoll Kühlen Eco HK G hc_g_room_setpoint_cool_eco FLOAT °C RW · EEPROM —
1484 Kühlgrenze HK A hc_a_cooling_limit UCHAR °C RW · EEPROM —
1485 Kühlgrenze HK B hc_b_cooling_limit UCHAR °C RW · EEPROM —
1486 Kühlgrenze HK C hc_c_cooling_limit UCHAR °C RW · EEPROM —
1487 Kühlgrenze HK D hc_d_cooling_limit UCHAR °C RW · EEPROM —
1488 Kühlgrenze HK E hc_e_cooling_limit UCHAR °C RW · EEPROM —
1489 Kühlgrenze HK F hc_f_cooling_limit UCHAR °C RW · EEPROM —
1490 Kühlgrenze HK G hc_g_cooling_limit UCHAR °C RW · EEPROM —
1491 Kühlvorlauf HK A hc_a_setpoint_flow_cooling UCHAR °C RW · EEPROM —
1492 Kühlvorlauf HK B hc_b_setpoint_flow_cooling UCHAR °C RW · EEPROM —
1493 Kühlvorlauf HK C hc_c_setpoint_flow_cooling UCHAR °C RW · EEPROM —
1494 Kühlvorlauf HK D hc_d_setpoint_flow_cooling UCHAR °C RW · EEPROM —
1495 Kühlvorlauf HK E hc_e_setpoint_flow_cooling UCHAR °C RW · EEPROM —
1496 Kühlvorlauf HK F hc_f_setpoint_flow_cooling UCHAR °C RW · EEPROM —
1497 Kühlvorlauf HK G hc_g_setpoint_flow_cooling UCHAR °C RW · EEPROM —
1498 Aktive Betriebsart HK A hc_a_active_mode UCHAR — R Enum
1499 Aktive Betriebsart HK B hc_b_active_mode UCHAR — R Enum
1500 Aktive Betriebsart HK C hc_c_active_mode UCHAR — R Enum
1501 Aktive Betriebsart HK D hc_d_active_mode UCHAR — R Enum
1502 Aktive Betriebsart HK E hc_e_active_mode UCHAR — R Enum
1503 Aktive Betriebsart HK F hc_f_active_mode UCHAR — R Enum
1504 Aktive Betriebsart HK G hc_g_active_mode UCHAR — R Enum
1505 Parallelverschiebung HK A hc_a_parallel_shift UCHAR °C RW · EEPROM —
1506 Parallelverschiebung HK B hc_b_parallel_shift UCHAR °C RW · EEPROM —
1507 Parallelverschiebung HK C hc_c_parallel_shift UCHAR °C RW · EEPROM —
1508 Parallelverschiebung HK D hc_d_parallel_shift UCHAR °C RW · EEPROM —
1509 Parallelverschiebung HK E hc_e_parallel_shift UCHAR °C RW · EEPROM —
1510 Parallelverschiebung HK F hc_f_parallel_shift UCHAR °C RW · EEPROM —
1511 Parallelverschiebung HK G hc_g_parallel_shift UCHAR °C RW · EEPROM —
1650–1651 Externe Raumtemperatur HK A hc_a_ext_room_temp FLOAT °C RW —
1652–1653 Externe Raumtemperatur HK B hc_b_ext_room_temp FLOAT °C RW —
1654–1655 Externe Raumtemperatur HK C hc_c_ext_room_temp FLOAT °C RW —
1656–1657 Externe Raumtemperatur HK D hc_d_ext_room_temp FLOAT °C RW —
1658–1659 Externe Raumtemperatur HK E hc_e_ext_room_temp FLOAT °C RW —
1660–1661 Externe Raumtemperatur HK F hc_f_ext_room_temp FLOAT °C RW —
1662–1663 Externe Raumtemperatur HK G hc_g_ext_room_temp FLOAT °C RW —
1680 Störung Wärmequellenkreis fault_heat_source_circuit UCHAR — R Navigator 10
1681 Störung Druckschalter Wärmequellenkreis fault_heat_source_pressure_switch UCHAR — R Navigator 10
1682 Störung Ladepumpe 1 Zwischenkreis fault_charging_pump_1_intermediate UCHAR — R Navigator 10
1683 Störung Ladepumpe 2 Zwischenkreis fault_charging_pump_2_intermediate UCHAR — R Navigator 10
1690–1691 Externe Außentemperatur (GLT) ext_outdoor_temp FLOAT °C RW —
1692–1693 Externe Feuchte (GLT) ext_humidity FLOAT % RW —
1694 Externe Anforderungstemperatur Heizen ext_demand_temp_heating UCHAR °C RW · EEPROM —
1695 Externe Anforderungstemperatur Kühlen ext_demand_temp_cooling UCHAR °C RW · EEPROM —
1696–1697 GLT Temperaturanforderung Heizen glt_temp_demand_heating FLOAT °C RW · cyclic —
1698–1699 GLT Temperaturanforderung Kühlen glt_temp_demand_cooling FLOAT °C RW · cyclic —

1700–1999 · Energy, solar, GLT & services (29)

Address(es) Description (DE) Register name Type Unit Access Note
1710 Externe Heizanforderung demand_heating BOOL — RW —
1711 Externe Kühlanforderung demand_cooling BOOL — RW —
1712 Externe WW-Ladeanforderung demand_dhw_charging BOOL — RW —
1713 Einmalige WW-Anforderung demand_onetime_dhw BOOL — RW —
1714 Externe Anforderung Grundwasserpumpe M15 ext_demand_groundwater_pump_m15 UCHAR % RW Navigator 10
1715 Externe Anforderung Grundwasserpumpe M15 (SW max) ext_demand_groundwater_pump_m15_sw_max UCHAR % RW Navigator 10
1716–1717 GLT Wärmespeichertemperatur glt_heat_storage_temp FLOAT °C RW —
1718–1719 GLT Kältespeichertemperatur glt_cold_storage_temp FLOAT °C RW —
1720–1721 GLT Warmwasser unten glt_dhw_temp_bottom FLOAT °C RW —
1722–1723 GLT Warmwasser oben glt_dhw_temp_top FLOAT °C RW —
1748–1749 Wärmemenge Heizen energy_heating FLOAT kWh R —
1750–1751 Wärmemenge Gesamt energy_total FLOAT kWh R —
1752–1753 Wärmemenge Kühlen energy_cooling FLOAT kWh R —
1754–1755 Wärmemenge Warmwasser energy_dhw FLOAT kWh R —
1756–1757 Wärmemenge Abtauen energy_defrost FLOAT kWh R —
1758–1759 Wärmemenge Passive Kühlung energy_passive_cooling FLOAT kWh R —
1760–1761 Wärmemenge Solar energy_solar FLOAT kWh R —
1762–1763 Wärmemenge E-Heizstab energy_electric_heater FLOAT kWh R —
1790–1791 Thermische Momentanleistung current_power FLOAT kW R —
1792–1793 Aktuelle Solarleistung current_power_solar FLOAT kW R —
1850–1851 Solar Kollektortemperatur solar_collector_temp FLOAT °C R —
1852–1853 Solar Rücklauftemperatur solar_return_temp FLOAT °C R —
1854–1855 Solar Ladetemperatur solar_charging_temp FLOAT °C R —
1856 Solar Betriebsart solar_mode UCHAR — RW · EEPROM Enum
1857–1858 Solar WQ-Referenztemperatur/Pooltemperatur solar_wq_pool_temp FLOAT °C R —
1870–1871 ISC Ladetemperatur Kühlen isc_charging_temp_cooling FLOAT °C R —
1872–1873 ISC Rückkühltemperatur isc_recooling_temp FLOAT °C R —
1874 ISC Modus isc_mode UCHAR — R Enum
1999 Fehlerquittierung error_acknowledge UCHAR — W · write-only —

2000–2999 · Zone modules (420)

Address(es) Description (DE) Register name Type Unit Access Note
2000 Zone 1 Betriebsart Heizen/Kühlen zm1_mode_heat_cool UCHAR — R Enum
2001 Zone 1 Entfeuchtung zm1_dehumidification UCHAR — R —
2002–2003 Zone 1 Raum 1 Raumtemperatur zm1_room1_temp FLOAT °C RW —
2004–2005 Zone 1 Raum 1 Raumsolltemperatur zm1_room1_setpoint FLOAT °C RW —
2006 Zone 1 Raum 1 Raumfeuchte zm1_room1_humidity UCHAR % RW —
2007 Zone 1 Raum 1 Raumbetriebsart zm1_room1_mode UCHAR — RW Enum
2008 Zone 1 Raum 1 Relais zm1_room1_relay UCHAR — R Binary
2009–2010 Zone 1 Raum 2 Raumtemperatur zm1_room2_temp FLOAT °C RW —
2011–2012 Zone 1 Raum 2 Raumsolltemperatur zm1_room2_setpoint FLOAT °C RW —
2013 Zone 1 Raum 2 Raumfeuchte zm1_room2_humidity UCHAR % RW —
2014 Zone 1 Raum 2 Raumbetriebsart zm1_room2_mode UCHAR — RW Enum
2015 Zone 1 Raum 2 Relais zm1_room2_relay UCHAR — R Binary
2016–2017 Zone 1 Raum 3 Raumtemperatur zm1_room3_temp FLOAT °C RW —
2018–2019 Zone 1 Raum 3 Raumsolltemperatur zm1_room3_setpoint FLOAT °C RW —
2020 Zone 1 Raum 3 Raumfeuchte zm1_room3_humidity UCHAR % RW —
2021 Zone 1 Raum 3 Raumbetriebsart zm1_room3_mode UCHAR — RW Enum
2022 Zone 1 Raum 3 Relais zm1_room3_relay UCHAR — R Binary
2023–2024 Zone 1 Raum 4 Raumtemperatur zm1_room4_temp FLOAT °C RW —
2025–2026 Zone 1 Raum 4 Raumsolltemperatur zm1_room4_setpoint FLOAT °C RW —
2027 Zone 1 Raum 4 Raumfeuchte zm1_room4_humidity UCHAR % RW —
2028 Zone 1 Raum 4 Raumbetriebsart zm1_room4_mode UCHAR — RW Enum
2029 Zone 1 Raum 4 Relais zm1_room4_relay UCHAR — R Binary
2030–2031 Zone 1 Raum 5 Raumtemperatur zm1_room5_temp FLOAT °C RW —
2032–2033 Zone 1 Raum 5 Raumsolltemperatur zm1_room5_setpoint FLOAT °C RW —
2034 Zone 1 Raum 5 Raumfeuchte zm1_room5_humidity UCHAR % RW —
2035 Zone 1 Raum 5 Raumbetriebsart zm1_room5_mode UCHAR — RW Enum
2036 Zone 1 Raum 5 Relais zm1_room5_relay UCHAR — R Binary
2037–2038 Zone 1 Raum 6 Raumtemperatur zm1_room6_temp FLOAT °C RW —
2039–2040 Zone 1 Raum 6 Raumsolltemperatur zm1_room6_setpoint FLOAT °C RW —
2041 Zone 1 Raum 6 Raumfeuchte zm1_room6_humidity UCHAR % RW —
2042 Zone 1 Raum 6 Raumbetriebsart zm1_room6_mode UCHAR — RW Enum
2043 Zone 1 Raum 6 Relais zm1_room6_relay UCHAR — R Binary
2044–2045 Zone 1 Raum 7 Raumtemperatur zm1_room7_temp FLOAT °C RW —
2046–2047 Zone 1 Raum 7 Raumsolltemperatur zm1_room7_setpoint FLOAT °C RW —
2048 Zone 1 Raum 7 Raumfeuchte zm1_room7_humidity UCHAR % RW —
2049 Zone 1 Raum 7 Raumbetriebsart zm1_room7_mode UCHAR — RW Enum
2050 Zone 1 Raum 7 Relais zm1_room7_relay UCHAR — R Binary
2051–2052 Zone 1 Raum 8 Raumtemperatur zm1_room8_temp FLOAT °C RW —
2053–2054 Zone 1 Raum 8 Raumsolltemperatur zm1_room8_setpoint FLOAT °C RW —
2055 Zone 1 Raum 8 Raumfeuchte zm1_room8_humidity UCHAR % RW —
2056 Zone 1 Raum 8 Raumbetriebsart zm1_room8_mode UCHAR — RW Enum
2057 Zone 1 Raum 8 Relais zm1_room8_relay UCHAR — R Binary
2065 Zone 2 Betriebsart Heizen/Kühlen zm2_mode_heat_cool UCHAR — R Enum
2066 Zone 2 Entfeuchtung zm2_dehumidification UCHAR — R —
2067–2068 Zone 2 Raum 1 Raumtemperatur zm2_room1_temp FLOAT °C RW —
2069–2070 Zone 2 Raum 1 Raumsolltemperatur zm2_room1_setpoint FLOAT °C RW —
2071 Zone 2 Raum 1 Raumfeuchte zm2_room1_humidity UCHAR % RW —
2072 Zone 2 Raum 1 Raumbetriebsart zm2_room1_mode UCHAR — RW Enum
2073 Zone 2 Raum 1 Relais zm2_room1_relay UCHAR — R Binary
2074–2075 Zone 2 Raum 2 Raumtemperatur zm2_room2_temp FLOAT °C RW —
2076–2077 Zone 2 Raum 2 Raumsolltemperatur zm2_room2_setpoint FLOAT °C RW —
2078 Zone 2 Raum 2 Raumfeuchte zm2_room2_humidity UCHAR % RW —
2079 Zone 2 Raum 2 Raumbetriebsart zm2_room2_mode UCHAR — RW Enum
2080 Zone 2 Raum 2 Relais zm2_room2_relay UCHAR — R Binary
2081–2082 Zone 2 Raum 3 Raumtemperatur zm2_room3_temp FLOAT °C RW —
2083–2084 Zone 2 Raum 3 Raumsolltemperatur zm2_room3_setpoint FLOAT °C RW —
2085 Zone 2 Raum 3 Raumfeuchte zm2_room3_humidity UCHAR % RW —
2086 Zone 2 Raum 3 Raumbetriebsart zm2_room3_mode UCHAR — RW Enum
2087 Zone 2 Raum 3 Relais zm2_room3_relay UCHAR — R Binary
2088–2089 Zone 2 Raum 4 Raumtemperatur zm2_room4_temp FLOAT °C RW —
2090–2091 Zone 2 Raum 4 Raumsolltemperatur zm2_room4_setpoint FLOAT °C RW —
2092 Zone 2 Raum 4 Raumfeuchte zm2_room4_humidity UCHAR % RW —
2093 Zone 2 Raum 4 Raumbetriebsart zm2_room4_mode UCHAR — RW Enum
2094 Zone 2 Raum 4 Relais zm2_room4_relay UCHAR — R Binary
2095–2096 Zone 2 Raum 5 Raumtemperatur zm2_room5_temp FLOAT °C RW —
2097–2098 Zone 2 Raum 5 Raumsolltemperatur zm2_room5_setpoint FLOAT °C RW —
2099 Zone 2 Raum 5 Raumfeuchte zm2_room5_humidity UCHAR % RW —
2100 Zone 2 Raum 5 Raumbetriebsart zm2_room5_mode UCHAR — RW Enum
2101 Zone 2 Raum 5 Relais zm2_room5_relay UCHAR — R Binary
2102–2103 Zone 2 Raum 6 Raumtemperatur zm2_room6_temp FLOAT °C RW —
2104–2105 Zone 2 Raum 6 Raumsolltemperatur zm2_room6_setpoint FLOAT °C RW —
2106 Zone 2 Raum 6 Raumfeuchte zm2_room6_humidity UCHAR % RW —
2107 Zone 2 Raum 6 Raumbetriebsart zm2_room6_mode UCHAR — RW Enum
2108 Zone 2 Raum 6 Relais zm2_room6_relay UCHAR — R Binary
2109–2110 Zone 2 Raum 7 Raumtemperatur zm2_room7_temp FLOAT °C RW —
2111–2112 Zone 2 Raum 7 Raumsolltemperatur zm2_room7_setpoint FLOAT °C RW —
2113 Zone 2 Raum 7 Raumfeuchte zm2_room7_humidity UCHAR % RW —
2114 Zone 2 Raum 7 Raumbetriebsart zm2_room7_mode UCHAR — RW Enum
2115 Zone 2 Raum 7 Relais zm2_room7_relay UCHAR — R Binary
2116–2117 Zone 2 Raum 8 Raumtemperatur zm2_room8_temp FLOAT °C RW —
2118–2119 Zone 2 Raum 8 Raumsolltemperatur zm2_room8_setpoint FLOAT °C RW —
2120 Zone 2 Raum 8 Raumfeuchte zm2_room8_humidity UCHAR % RW —
2121 Zone 2 Raum 8 Raumbetriebsart zm2_room8_mode UCHAR — RW Enum
2122 Zone 2 Raum 8 Relais zm2_room8_relay UCHAR — R Binary
2130 Zone 3 Betriebsart Heizen/Kühlen zm3_mode_heat_cool UCHAR — R Enum
2131 Zone 3 Entfeuchtung zm3_dehumidification UCHAR — R —
2132–2133 Zone 3 Raum 1 Raumtemperatur zm3_room1_temp FLOAT °C RW —
2134–2135 Zone 3 Raum 1 Raumsolltemperatur zm3_room1_setpoint FLOAT °C RW —
2136 Zone 3 Raum 1 Raumfeuchte zm3_room1_humidity UCHAR % RW —
2137 Zone 3 Raum 1 Raumbetriebsart zm3_room1_mode UCHAR — RW Enum
2138 Zone 3 Raum 1 Relais zm3_room1_relay UCHAR — R Binary
2139–2140 Zone 3 Raum 2 Raumtemperatur zm3_room2_temp FLOAT °C RW —
2141–2142 Zone 3 Raum 2 Raumsolltemperatur zm3_room2_setpoint FLOAT °C RW —
2143 Zone 3 Raum 2 Raumfeuchte zm3_room2_humidity UCHAR % RW —
2144 Zone 3 Raum 2 Raumbetriebsart zm3_room2_mode UCHAR — RW Enum
2145 Zone 3 Raum 2 Relais zm3_room2_relay UCHAR — R Binary
2146–2147 Zone 3 Raum 3 Raumtemperatur zm3_room3_temp FLOAT °C RW —
2148–2149 Zone 3 Raum 3 Raumsolltemperatur zm3_room3_setpoint FLOAT °C RW —
2150 Zone 3 Raum 3 Raumfeuchte zm3_room3_humidity UCHAR % RW —
2151 Zone 3 Raum 3 Raumbetriebsart zm3_room3_mode UCHAR — RW Enum
2152 Zone 3 Raum 3 Relais zm3_room3_relay UCHAR — R Binary
2153–2154 Zone 3 Raum 4 Raumtemperatur zm3_room4_temp FLOAT °C RW —
2155–2156 Zone 3 Raum 4 Raumsolltemperatur zm3_room4_setpoint FLOAT °C RW —
2157 Zone 3 Raum 4 Raumfeuchte zm3_room4_humidity UCHAR % RW —
2158 Zone 3 Raum 4 Raumbetriebsart zm3_room4_mode UCHAR — RW Enum
2159 Zone 3 Raum 4 Relais zm3_room4_relay UCHAR — R Binary
2160–2161 Zone 3 Raum 5 Raumtemperatur zm3_room5_temp FLOAT °C RW —
2162–2163 Zone 3 Raum 5 Raumsolltemperatur zm3_room5_setpoint FLOAT °C RW —
2164 Zone 3 Raum 5 Raumfeuchte zm3_room5_humidity UCHAR % RW —
2165 Zone 3 Raum 5 Raumbetriebsart zm3_room5_mode UCHAR — RW Enum
2166 Zone 3 Raum 5 Relais zm3_room5_relay UCHAR — R Binary
2167–2168 Zone 3 Raum 6 Raumtemperatur zm3_room6_temp FLOAT °C RW —
2169–2170 Zone 3 Raum 6 Raumsolltemperatur zm3_room6_setpoint FLOAT °C RW —
2171 Zone 3 Raum 6 Raumfeuchte zm3_room6_humidity UCHAR % RW —
2172 Zone 3 Raum 6 Raumbetriebsart zm3_room6_mode UCHAR — RW Enum
2173 Zone 3 Raum 6 Relais zm3_room6_relay UCHAR — R Binary
2174–2175 Zone 3 Raum 7 Raumtemperatur zm3_room7_temp FLOAT °C RW —
2176–2177 Zone 3 Raum 7 Raumsolltemperatur zm3_room7_setpoint FLOAT °C RW —
2178 Zone 3 Raum 7 Raumfeuchte zm3_room7_humidity UCHAR % RW —
2179 Zone 3 Raum 7 Raumbetriebsart zm3_room7_mode UCHAR — RW Enum
2180 Zone 3 Raum 7 Relais zm3_room7_relay UCHAR — R Binary
2181–2182 Zone 3 Raum 8 Raumtemperatur zm3_room8_temp FLOAT °C RW —
2183–2184 Zone 3 Raum 8 Raumsolltemperatur zm3_room8_setpoint FLOAT °C RW —
2185 Zone 3 Raum 8 Raumfeuchte zm3_room8_humidity UCHAR % RW —
2186 Zone 3 Raum 8 Raumbetriebsart zm3_room8_mode UCHAR — RW Enum
2187 Zone 3 Raum 8 Relais zm3_room8_relay UCHAR — R Binary
2195 Zone 4 Betriebsart Heizen/Kühlen zm4_mode_heat_cool UCHAR — R Enum
2196 Zone 4 Entfeuchtung zm4_dehumidification UCHAR — R —
2197–2198 Zone 4 Raum 1 Raumtemperatur zm4_room1_temp FLOAT °C RW —
2199–2200 Zone 4 Raum 1 Raumsolltemperatur zm4_room1_setpoint FLOAT °C RW —
2201 Zone 4 Raum 1 Raumfeuchte zm4_room1_humidity UCHAR % RW —
2202 Zone 4 Raum 1 Raumbetriebsart zm4_room1_mode UCHAR — RW Enum
2203 Zone 4 Raum 1 Relais zm4_room1_relay UCHAR — R Binary
2204–2205 Zone 4 Raum 2 Raumtemperatur zm4_room2_temp FLOAT °C RW —
2206–2207 Zone 4 Raum 2 Raumsolltemperatur zm4_room2_setpoint FLOAT °C RW —
2208 Zone 4 Raum 2 Raumfeuchte zm4_room2_humidity UCHAR % RW —
2209 Zone 4 Raum 2 Raumbetriebsart zm4_room2_mode UCHAR — RW Enum
2210 Zone 4 Raum 2 Relais zm4_room2_relay UCHAR — R Binary
2211–2212 Zone 4 Raum 3 Raumtemperatur zm4_room3_temp FLOAT °C RW —
2213–2214 Zone 4 Raum 3 Raumsolltemperatur zm4_room3_setpoint FLOAT °C RW —
2215 Zone 4 Raum 3 Raumfeuchte zm4_room3_humidity UCHAR % RW —
2216 Zone 4 Raum 3 Raumbetriebsart zm4_room3_mode UCHAR — RW Enum
2217 Zone 4 Raum 3 Relais zm4_room3_relay UCHAR — R Binary
2218–2219 Zone 4 Raum 4 Raumtemperatur zm4_room4_temp FLOAT °C RW —
2220–2221 Zone 4 Raum 4 Raumsolltemperatur zm4_room4_setpoint FLOAT °C RW —
2222 Zone 4 Raum 4 Raumfeuchte zm4_room4_humidity UCHAR % RW —
2223 Zone 4 Raum 4 Raumbetriebsart zm4_room4_mode UCHAR — RW Enum
2224 Zone 4 Raum 4 Relais zm4_room4_relay UCHAR — R Binary
2225–2226 Zone 4 Raum 5 Raumtemperatur zm4_room5_temp FLOAT °C RW —
2227–2228 Zone 4 Raum 5 Raumsolltemperatur zm4_room5_setpoint FLOAT °C RW —
2229 Zone 4 Raum 5 Raumfeuchte zm4_room5_humidity UCHAR % RW —
2230 Zone 4 Raum 5 Raumbetriebsart zm4_room5_mode UCHAR — RW Enum
2231 Zone 4 Raum 5 Relais zm4_room5_relay UCHAR — R Binary
2232–2233 Zone 4 Raum 6 Raumtemperatur zm4_room6_temp FLOAT °C RW —
2234–2235 Zone 4 Raum 6 Raumsolltemperatur zm4_room6_setpoint FLOAT °C RW —
2236 Zone 4 Raum 6 Raumfeuchte zm4_room6_humidity UCHAR % RW —
2237 Zone 4 Raum 6 Raumbetriebsart zm4_room6_mode UCHAR — RW Enum
2238 Zone 4 Raum 6 Relais zm4_room6_relay UCHAR — R Binary
2239–2240 Zone 4 Raum 7 Raumtemperatur zm4_room7_temp FLOAT °C RW —
2241–2242 Zone 4 Raum 7 Raumsolltemperatur zm4_room7_setpoint FLOAT °C RW —
2243 Zone 4 Raum 7 Raumfeuchte zm4_room7_humidity UCHAR % RW —
2244 Zone 4 Raum 7 Raumbetriebsart zm4_room7_mode UCHAR — RW Enum
2245 Zone 4 Raum 7 Relais zm4_room7_relay UCHAR — R Binary
2246–2247 Zone 4 Raum 8 Raumtemperatur zm4_room8_temp FLOAT °C RW —
2248–2249 Zone 4 Raum 8 Raumsolltemperatur zm4_room8_setpoint FLOAT °C RW —
2250 Zone 4 Raum 8 Raumfeuchte zm4_room8_humidity UCHAR % RW —
2251 Zone 4 Raum 8 Raumbetriebsart zm4_room8_mode UCHAR — RW Enum
2252 Zone 4 Raum 8 Relais zm4_room8_relay UCHAR — R Binary
2260 Zone 5 Betriebsart Heizen/Kühlen zm5_mode_heat_cool UCHAR — R Enum
2261 Zone 5 Entfeuchtung zm5_dehumidification UCHAR — R —
2262–2263 Zone 5 Raum 1 Raumtemperatur zm5_room1_temp FLOAT °C RW —
2264–2265 Zone 5 Raum 1 Raumsolltemperatur zm5_room1_setpoint FLOAT °C RW —
2266 Zone 5 Raum 1 Raumfeuchte zm5_room1_humidity UCHAR % RW —
2267 Zone 5 Raum 1 Raumbetriebsart zm5_room1_mode UCHAR — RW Enum
2268 Zone 5 Raum 1 Relais zm5_room1_relay UCHAR — R Binary
2269–2270 Zone 5 Raum 2 Raumtemperatur zm5_room2_temp FLOAT °C RW —
2271–2272 Zone 5 Raum 2 Raumsolltemperatur zm5_room2_setpoint FLOAT °C RW —
2273 Zone 5 Raum 2 Raumfeuchte zm5_room2_humidity UCHAR % RW —
2274 Zone 5 Raum 2 Raumbetriebsart zm5_room2_mode UCHAR — RW Enum
2275 Zone 5 Raum 2 Relais zm5_room2_relay UCHAR — R Binary
2276–2277 Zone 5 Raum 3 Raumtemperatur zm5_room3_temp FLOAT °C RW —
2278–2279 Zone 5 Raum 3 Raumsolltemperatur zm5_room3_setpoint FLOAT °C RW —
2280 Zone 5 Raum 3 Raumfeuchte zm5_room3_humidity UCHAR % RW —
2281 Zone 5 Raum 3 Raumbetriebsart zm5_room3_mode UCHAR — RW Enum
2282 Zone 5 Raum 3 Relais zm5_room3_relay UCHAR — R Binary
2283–2284 Zone 5 Raum 4 Raumtemperatur zm5_room4_temp FLOAT °C RW —
2285–2286 Zone 5 Raum 4 Raumsolltemperatur zm5_room4_setpoint FLOAT °C RW —
2287 Zone 5 Raum 4 Raumfeuchte zm5_room4_humidity UCHAR % RW —
2288 Zone 5 Raum 4 Raumbetriebsart zm5_room4_mode UCHAR — RW Enum
2289 Zone 5 Raum 4 Relais zm5_room4_relay UCHAR — R Binary
2290–2291 Zone 5 Raum 5 Raumtemperatur zm5_room5_temp FLOAT °C RW —
2292–2293 Zone 5 Raum 5 Raumsolltemperatur zm5_room5_setpoint FLOAT °C RW —
2294 Zone 5 Raum 5 Raumfeuchte zm5_room5_humidity UCHAR % RW —
2295 Zone 5 Raum 5 Raumbetriebsart zm5_room5_mode UCHAR — RW Enum
2296 Zone 5 Raum 5 Relais zm5_room5_relay UCHAR — R Binary
2297–2298 Zone 5 Raum 6 Raumtemperatur zm5_room6_temp FLOAT °C RW —
2299–2300 Zone 5 Raum 6 Raumsolltemperatur zm5_room6_setpoint FLOAT °C RW —
2301 Zone 5 Raum 6 Raumfeuchte zm5_room6_humidity UCHAR % RW —
2302 Zone 5 Raum 6 Raumbetriebsart zm5_room6_mode UCHAR — RW Enum
2303 Zone 5 Raum 6 Relais zm5_room6_relay UCHAR — R Binary
2304–2305 Zone 5 Raum 7 Raumtemperatur zm5_room7_temp FLOAT °C RW —
2306–2307 Zone 5 Raum 7 Raumsolltemperatur zm5_room7_setpoint FLOAT °C RW —
2308 Zone 5 Raum 7 Raumfeuchte zm5_room7_humidity UCHAR % RW —
2309 Zone 5 Raum 7 Raumbetriebsart zm5_room7_mode UCHAR — RW Enum
2310 Zone 5 Raum 7 Relais zm5_room7_relay UCHAR — R Binary
2311–2312 Zone 5 Raum 8 Raumtemperatur zm5_room8_temp FLOAT °C RW —
2313–2314 Zone 5 Raum 8 Raumsolltemperatur zm5_room8_setpoint FLOAT °C RW —
2315 Zone 5 Raum 8 Raumfeuchte zm5_room8_humidity UCHAR % RW —
2316 Zone 5 Raum 8 Raumbetriebsart zm5_room8_mode UCHAR — RW Enum
2317 Zone 5 Raum 8 Relais zm5_room8_relay UCHAR — R Binary
2325 Zone 6 Betriebsart Heizen/Kühlen zm6_mode_heat_cool UCHAR — R Enum
2326 Zone 6 Entfeuchtung zm6_dehumidification UCHAR — R —
2327–2328 Zone 6 Raum 1 Raumtemperatur zm6_room1_temp FLOAT °C RW —
2329–2330 Zone 6 Raum 1 Raumsolltemperatur zm6_room1_setpoint FLOAT °C RW —
2331 Zone 6 Raum 1 Raumfeuchte zm6_room1_humidity UCHAR % RW —
2332 Zone 6 Raum 1 Raumbetriebsart zm6_room1_mode UCHAR — RW Enum
2333 Zone 6 Raum 1 Relais zm6_room1_relay UCHAR — R Binary
2334–2335 Zone 6 Raum 2 Raumtemperatur zm6_room2_temp FLOAT °C RW —
2336–2337 Zone 6 Raum 2 Raumsolltemperatur zm6_room2_setpoint FLOAT °C RW —
2338 Zone 6 Raum 2 Raumfeuchte zm6_room2_humidity UCHAR % RW —
2339 Zone 6 Raum 2 Raumbetriebsart zm6_room2_mode UCHAR — RW Enum
2340 Zone 6 Raum 2 Relais zm6_room2_relay UCHAR — R Binary
2341–2342 Zone 6 Raum 3 Raumtemperatur zm6_room3_temp FLOAT °C RW —
2343–2344 Zone 6 Raum 3 Raumsolltemperatur zm6_room3_setpoint FLOAT °C RW —
2345 Zone 6 Raum 3 Raumfeuchte zm6_room3_humidity UCHAR % RW —
2346 Zone 6 Raum 3 Raumbetriebsart zm6_room3_mode UCHAR — RW Enum
2347 Zone 6 Raum 3 Relais zm6_room3_relay UCHAR — R Binary
2348–2349 Zone 6 Raum 4 Raumtemperatur zm6_room4_temp FLOAT °C RW —
2350–2351 Zone 6 Raum 4 Raumsolltemperatur zm6_room4_setpoint FLOAT °C RW —
2352 Zone 6 Raum 4 Raumfeuchte zm6_room4_humidity UCHAR % RW —
2353 Zone 6 Raum 4 Raumbetriebsart zm6_room4_mode UCHAR — RW Enum
2354 Zone 6 Raum 4 Relais zm6_room4_relay UCHAR — R Binary
2355–2356 Zone 6 Raum 5 Raumtemperatur zm6_room5_temp FLOAT °C RW —
2357–2358 Zone 6 Raum 5 Raumsolltemperatur zm6_room5_setpoint FLOAT °C RW —
2359 Zone 6 Raum 5 Raumfeuchte zm6_room5_humidity UCHAR % RW —
2360 Zone 6 Raum 5 Raumbetriebsart zm6_room5_mode UCHAR — RW Enum
2361 Zone 6 Raum 5 Relais zm6_room5_relay UCHAR — R Binary
2362–2363 Zone 6 Raum 6 Raumtemperatur zm6_room6_temp FLOAT °C RW —
2364–2365 Zone 6 Raum 6 Raumsolltemperatur zm6_room6_setpoint FLOAT °C RW —
2366 Zone 6 Raum 6 Raumfeuchte zm6_room6_humidity UCHAR % RW —
2367 Zone 6 Raum 6 Raumbetriebsart zm6_room6_mode UCHAR — RW Enum
2368 Zone 6 Raum 6 Relais zm6_room6_relay UCHAR — R Binary
2369–2370 Zone 6 Raum 7 Raumtemperatur zm6_room7_temp FLOAT °C RW —
2371–2372 Zone 6 Raum 7 Raumsolltemperatur zm6_room7_setpoint FLOAT °C RW —
2373 Zone 6 Raum 7 Raumfeuchte zm6_room7_humidity UCHAR % RW —
2374 Zone 6 Raum 7 Raumbetriebsart zm6_room7_mode UCHAR — RW Enum
2375 Zone 6 Raum 7 Relais zm6_room7_relay UCHAR — R Binary
2376–2377 Zone 6 Raum 8 Raumtemperatur zm6_room8_temp FLOAT °C RW —
2378–2379 Zone 6 Raum 8 Raumsolltemperatur zm6_room8_setpoint FLOAT °C RW —
2380 Zone 6 Raum 8 Raumfeuchte zm6_room8_humidity UCHAR % RW —
2381 Zone 6 Raum 8 Raumbetriebsart zm6_room8_mode UCHAR — RW Enum
2382 Zone 6 Raum 8 Relais zm6_room8_relay UCHAR — R Binary
2390 Zone 7 Betriebsart Heizen/Kühlen zm7_mode_heat_cool UCHAR — R Enum
2391 Zone 7 Entfeuchtung zm7_dehumidification UCHAR — R —
2392–2393 Zone 7 Raum 1 Raumtemperatur zm7_room1_temp FLOAT °C RW —
2394–2395 Zone 7 Raum 1 Raumsolltemperatur zm7_room1_setpoint FLOAT °C RW —
2396 Zone 7 Raum 1 Raumfeuchte zm7_room1_humidity UCHAR % RW —
2397 Zone 7 Raum 1 Raumbetriebsart zm7_room1_mode UCHAR — RW Enum
2398 Zone 7 Raum 1 Relais zm7_room1_relay UCHAR — R Binary
2399–2400 Zone 7 Raum 2 Raumtemperatur zm7_room2_temp FLOAT °C RW —
2401–2402 Zone 7 Raum 2 Raumsolltemperatur zm7_room2_setpoint FLOAT °C RW —
2403 Zone 7 Raum 2 Raumfeuchte zm7_room2_humidity UCHAR % RW —
2404 Zone 7 Raum 2 Raumbetriebsart zm7_room2_mode UCHAR — RW Enum
2405 Zone 7 Raum 2 Relais zm7_room2_relay UCHAR — R Binary
2406–2407 Zone 7 Raum 3 Raumtemperatur zm7_room3_temp FLOAT °C RW —
2408–2409 Zone 7 Raum 3 Raumsolltemperatur zm7_room3_setpoint FLOAT °C RW —
2410 Zone 7 Raum 3 Raumfeuchte zm7_room3_humidity UCHAR % RW —
2411 Zone 7 Raum 3 Raumbetriebsart zm7_room3_mode UCHAR — RW Enum
2412 Zone 7 Raum 3 Relais zm7_room3_relay UCHAR — R Binary
2413–2414 Zone 7 Raum 4 Raumtemperatur zm7_room4_temp FLOAT °C RW —
2415–2416 Zone 7 Raum 4 Raumsolltemperatur zm7_room4_setpoint FLOAT °C RW —
2417 Zone 7 Raum 4 Raumfeuchte zm7_room4_humidity UCHAR % RW —
2418 Zone 7 Raum 4 Raumbetriebsart zm7_room4_mode UCHAR — RW Enum
2419 Zone 7 Raum 4 Relais zm7_room4_relay UCHAR — R Binary
2420–2421 Zone 7 Raum 5 Raumtemperatur zm7_room5_temp FLOAT °C RW —
2422–2423 Zone 7 Raum 5 Raumsolltemperatur zm7_room5_setpoint FLOAT °C RW —
2424 Zone 7 Raum 5 Raumfeuchte zm7_room5_humidity UCHAR % RW —
2425 Zone 7 Raum 5 Raumbetriebsart zm7_room5_mode UCHAR — RW Enum
2426 Zone 7 Raum 5 Relais zm7_room5_relay UCHAR — R Binary
2427–2428 Zone 7 Raum 6 Raumtemperatur zm7_room6_temp FLOAT °C RW —
2429–2430 Zone 7 Raum 6 Raumsolltemperatur zm7_room6_setpoint FLOAT °C RW —
2431 Zone 7 Raum 6 Raumfeuchte zm7_room6_humidity UCHAR % RW —
2432 Zone 7 Raum 6 Raumbetriebsart zm7_room6_mode UCHAR — RW Enum
2433 Zone 7 Raum 6 Relais zm7_room6_relay UCHAR — R Binary
2434–2435 Zone 7 Raum 7 Raumtemperatur zm7_room7_temp FLOAT °C RW —
2436–2437 Zone 7 Raum 7 Raumsolltemperatur zm7_room7_setpoint FLOAT °C RW —
2438 Zone 7 Raum 7 Raumfeuchte zm7_room7_humidity UCHAR % RW —
2439 Zone 7 Raum 7 Raumbetriebsart zm7_room7_mode UCHAR — RW Enum
2440 Zone 7 Raum 7 Relais zm7_room7_relay UCHAR — R Binary
2441–2442 Zone 7 Raum 8 Raumtemperatur zm7_room8_temp FLOAT °C RW —
2443–2444 Zone 7 Raum 8 Raumsolltemperatur zm7_room8_setpoint FLOAT °C RW —
2445 Zone 7 Raum 8 Raumfeuchte zm7_room8_humidity UCHAR % RW —
2446 Zone 7 Raum 8 Raumbetriebsart zm7_room8_mode UCHAR — RW Enum
2447 Zone 7 Raum 8 Relais zm7_room8_relay UCHAR — R Binary
2455 Zone 8 Betriebsart Heizen/Kühlen zm8_mode_heat_cool UCHAR — R Enum
2456 Zone 8 Entfeuchtung zm8_dehumidification UCHAR — R —
2457–2458 Zone 8 Raum 1 Raumtemperatur zm8_room1_temp FLOAT °C RW —
2459–2460 Zone 8 Raum 1 Raumsolltemperatur zm8_room1_setpoint FLOAT °C RW —
2461 Zone 8 Raum 1 Raumfeuchte zm8_room1_humidity UCHAR % RW —
2462 Zone 8 Raum 1 Raumbetriebsart zm8_room1_mode UCHAR — RW Enum
2463 Zone 8 Raum 1 Relais zm8_room1_relay UCHAR — R Binary
2464–2465 Zone 8 Raum 2 Raumtemperatur zm8_room2_temp FLOAT °C RW —
2466–2467 Zone 8 Raum 2 Raumsolltemperatur zm8_room2_setpoint FLOAT °C RW —
2468 Zone 8 Raum 2 Raumfeuchte zm8_room2_humidity UCHAR % RW —
2469 Zone 8 Raum 2 Raumbetriebsart zm8_room2_mode UCHAR — RW Enum
2470 Zone 8 Raum 2 Relais zm8_room2_relay UCHAR — R Binary
2471–2472 Zone 8 Raum 3 Raumtemperatur zm8_room3_temp FLOAT °C RW —
2473–2474 Zone 8 Raum 3 Raumsolltemperatur zm8_room3_setpoint FLOAT °C RW —
2475 Zone 8 Raum 3 Raumfeuchte zm8_room3_humidity UCHAR % RW —
2476 Zone 8 Raum 3 Raumbetriebsart zm8_room3_mode UCHAR — RW Enum
2477 Zone 8 Raum 3 Relais zm8_room3_relay UCHAR — R Binary
2478–2479 Zone 8 Raum 4 Raumtemperatur zm8_room4_temp FLOAT °C RW —
2480–2481 Zone 8 Raum 4 Raumsolltemperatur zm8_room4_setpoint FLOAT °C RW —
2482 Zone 8 Raum 4 Raumfeuchte zm8_room4_humidity UCHAR % RW —
2483 Zone 8 Raum 4 Raumbetriebsart zm8_room4_mode UCHAR — RW Enum
2484 Zone 8 Raum 4 Relais zm8_room4_relay UCHAR — R Binary
2485–2486 Zone 8 Raum 5 Raumtemperatur zm8_room5_temp FLOAT °C RW —
2487–2488 Zone 8 Raum 5 Raumsolltemperatur zm8_room5_setpoint FLOAT °C RW —
2489 Zone 8 Raum 5 Raumfeuchte zm8_room5_humidity UCHAR % RW —
2490 Zone 8 Raum 5 Raumbetriebsart zm8_room5_mode UCHAR — RW Enum
2491 Zone 8 Raum 5 Relais zm8_room5_relay UCHAR — R Binary
2492–2493 Zone 8 Raum 6 Raumtemperatur zm8_room6_temp FLOAT °C RW —
2494–2495 Zone 8 Raum 6 Raumsolltemperatur zm8_room6_setpoint FLOAT °C RW —
2496 Zone 8 Raum 6 Raumfeuchte zm8_room6_humidity UCHAR % RW —
2497 Zone 8 Raum 6 Raumbetriebsart zm8_room6_mode UCHAR — RW Enum
2498 Zone 8 Raum 6 Relais zm8_room6_relay UCHAR — R Binary
2499–2500 Zone 8 Raum 7 Raumtemperatur zm8_room7_temp FLOAT °C RW —
2501–2502 Zone 8 Raum 7 Raumsolltemperatur zm8_room7_setpoint FLOAT °C RW —
2503 Zone 8 Raum 7 Raumfeuchte zm8_room7_humidity UCHAR % RW —
2504 Zone 8 Raum 7 Raumbetriebsart zm8_room7_mode UCHAR — RW Enum
2505 Zone 8 Raum 7 Relais zm8_room7_relay UCHAR — R Binary
2506–2507 Zone 8 Raum 8 Raumtemperatur zm8_room8_temp FLOAT °C RW —
2508–2509 Zone 8 Raum 8 Raumsolltemperatur zm8_room8_setpoint FLOAT °C RW —
2510 Zone 8 Raum 8 Raumfeuchte zm8_room8_humidity UCHAR % RW —
2511 Zone 8 Raum 8 Raumbetriebsart zm8_room8_mode UCHAR — RW Enum
2512 Zone 8 Raum 8 Relais zm8_room8_relay UCHAR — R Binary
2520 Zone 9 Betriebsart Heizen/Kühlen zm9_mode_heat_cool UCHAR — R Enum
2521 Zone 9 Entfeuchtung zm9_dehumidification UCHAR — R —
2522–2523 Zone 9 Raum 1 Raumtemperatur zm9_room1_temp FLOAT °C RW —
2524–2525 Zone 9 Raum 1 Raumsolltemperatur zm9_room1_setpoint FLOAT °C RW —
2526 Zone 9 Raum 1 Raumfeuchte zm9_room1_humidity UCHAR % RW —
2527 Zone 9 Raum 1 Raumbetriebsart zm9_room1_mode UCHAR — RW Enum
2528 Zone 9 Raum 1 Relais zm9_room1_relay UCHAR — R Binary
2529–2530 Zone 9 Raum 2 Raumtemperatur zm9_room2_temp FLOAT °C RW —
2531–2532 Zone 9 Raum 2 Raumsolltemperatur zm9_room2_setpoint FLOAT °C RW —
2533 Zone 9 Raum 2 Raumfeuchte zm9_room2_humidity UCHAR % RW —
2534 Zone 9 Raum 2 Raumbetriebsart zm9_room2_mode UCHAR — RW Enum
2535 Zone 9 Raum 2 Relais zm9_room2_relay UCHAR — R Binary
2536–2537 Zone 9 Raum 3 Raumtemperatur zm9_room3_temp FLOAT °C RW —
2538–2539 Zone 9 Raum 3 Raumsolltemperatur zm9_room3_setpoint FLOAT °C RW —
2540 Zone 9 Raum 3 Raumfeuchte zm9_room3_humidity UCHAR % RW —
2541 Zone 9 Raum 3 Raumbetriebsart zm9_room3_mode UCHAR — RW Enum
2542 Zone 9 Raum 3 Relais zm9_room3_relay UCHAR — R Binary
2543–2544 Zone 9 Raum 4 Raumtemperatur zm9_room4_temp FLOAT °C RW —
2545–2546 Zone 9 Raum 4 Raumsolltemperatur zm9_room4_setpoint FLOAT °C RW —
2547 Zone 9 Raum 4 Raumfeuchte zm9_room4_humidity UCHAR % RW —
2548 Zone 9 Raum 4 Raumbetriebsart zm9_room4_mode UCHAR — RW Enum
2549 Zone 9 Raum 4 Relais zm9_room4_relay UCHAR — R Binary
2550–2551 Zone 9 Raum 5 Raumtemperatur zm9_room5_temp FLOAT °C RW —
2552–2553 Zone 9 Raum 5 Raumsolltemperatur zm9_room5_setpoint FLOAT °C RW —
2554 Zone 9 Raum 5 Raumfeuchte zm9_room5_humidity UCHAR % RW —
2555 Zone 9 Raum 5 Raumbetriebsart zm9_room5_mode UCHAR — RW Enum
2556 Zone 9 Raum 5 Relais zm9_room5_relay UCHAR — R Binary
2557–2558 Zone 9 Raum 6 Raumtemperatur zm9_room6_temp FLOAT °C RW —
2559–2560 Zone 9 Raum 6 Raumsolltemperatur zm9_room6_setpoint FLOAT °C RW —
2561 Zone 9 Raum 6 Raumfeuchte zm9_room6_humidity UCHAR % RW —
2562 Zone 9 Raum 6 Raumbetriebsart zm9_room6_mode UCHAR — RW Enum
2563 Zone 9 Raum 6 Relais zm9_room6_relay UCHAR — R Binary
2564–2565 Zone 9 Raum 7 Raumtemperatur zm9_room7_temp FLOAT °C RW —
2566–2567 Zone 9 Raum 7 Raumsolltemperatur zm9_room7_setpoint FLOAT °C RW —
2568 Zone 9 Raum 7 Raumfeuchte zm9_room7_humidity UCHAR % RW —
2569 Zone 9 Raum 7 Raumbetriebsart zm9_room7_mode UCHAR — RW Enum
2570 Zone 9 Raum 7 Relais zm9_room7_relay UCHAR — R Binary
2571–2572 Zone 9 Raum 8 Raumtemperatur zm9_room8_temp FLOAT °C RW —
2573–2574 Zone 9 Raum 8 Raumsolltemperatur zm9_room8_setpoint FLOAT °C RW —
2575 Zone 9 Raum 8 Raumfeuchte zm9_room8_humidity UCHAR % RW —
2576 Zone 9 Raum 8 Raumbetriebsart zm9_room8_mode UCHAR — RW Enum
2577 Zone 9 Raum 8 Relais zm9_room8_relay UCHAR — R Binary
2585 Zone 10 Betriebsart Heizen/Kühlen zm10_mode_heat_cool UCHAR — R Enum
2586 Zone 10 Entfeuchtung zm10_dehumidification UCHAR — R —
2587–2588 Zone 10 Raum 1 Raumtemperatur zm10_room1_temp FLOAT °C RW —
2589–2590 Zone 10 Raum 1 Raumsolltemperatur zm10_room1_setpoint FLOAT °C RW —
2591 Zone 10 Raum 1 Raumfeuchte zm10_room1_humidity UCHAR % RW —
2592 Zone 10 Raum 1 Raumbetriebsart zm10_room1_mode UCHAR — RW Enum
2593 Zone 10 Raum 1 Relais zm10_room1_relay UCHAR — R Binary
2594–2595 Zone 10 Raum 2 Raumtemperatur zm10_room2_temp FLOAT °C RW —
2596–2597 Zone 10 Raum 2 Raumsolltemperatur zm10_room2_setpoint FLOAT °C RW —
2598 Zone 10 Raum 2 Raumfeuchte zm10_room2_humidity UCHAR % RW —
2599 Zone 10 Raum 2 Raumbetriebsart zm10_room2_mode UCHAR — RW Enum
2600 Zone 10 Raum 2 Relais zm10_room2_relay UCHAR — R Binary
2601–2602 Zone 10 Raum 3 Raumtemperatur zm10_room3_temp FLOAT °C RW —
2603–2604 Zone 10 Raum 3 Raumsolltemperatur zm10_room3_setpoint FLOAT °C RW —
2605 Zone 10 Raum 3 Raumfeuchte zm10_room3_humidity UCHAR % RW —
2606 Zone 10 Raum 3 Raumbetriebsart zm10_room3_mode UCHAR — RW Enum
2607 Zone 10 Raum 3 Relais zm10_room3_relay UCHAR — R Binary
2608–2609 Zone 10 Raum 4 Raumtemperatur zm10_room4_temp FLOAT °C RW —
2610–2611 Zone 10 Raum 4 Raumsolltemperatur zm10_room4_setpoint FLOAT °C RW —
2612 Zone 10 Raum 4 Raumfeuchte zm10_room4_humidity UCHAR % RW —
2613 Zone 10 Raum 4 Raumbetriebsart zm10_room4_mode UCHAR — RW Enum
2614 Zone 10 Raum 4 Relais zm10_room4_relay UCHAR — R Binary
2615–2616 Zone 10 Raum 5 Raumtemperatur zm10_room5_temp FLOAT °C RW —
2617–2618 Zone 10 Raum 5 Raumsolltemperatur zm10_room5_setpoint FLOAT °C RW —
2619 Zone 10 Raum 5 Raumfeuchte zm10_room5_humidity UCHAR % RW —
2620 Zone 10 Raum 5 Raumbetriebsart zm10_room5_mode UCHAR — RW Enum
2621 Zone 10 Raum 5 Relais zm10_room5_relay UCHAR — R Binary
2622–2623 Zone 10 Raum 6 Raumtemperatur zm10_room6_temp FLOAT °C RW —
2624–2625 Zone 10 Raum 6 Raumsolltemperatur zm10_room6_setpoint FLOAT °C RW —
2626 Zone 10 Raum 6 Raumfeuchte zm10_room6_humidity UCHAR % RW —
2627 Zone 10 Raum 6 Raumbetriebsart zm10_room6_mode UCHAR — RW Enum
2628 Zone 10 Raum 6 Relais zm10_room6_relay UCHAR — R Binary
2629–2630 Zone 10 Raum 7 Raumtemperatur zm10_room7_temp FLOAT °C RW —
2631–2632 Zone 10 Raum 7 Raumsolltemperatur zm10_room7_setpoint FLOAT °C RW —
2633 Zone 10 Raum 7 Raumfeuchte zm10_room7_humidity UCHAR % RW —
2634 Zone 10 Raum 7 Raumbetriebsart zm10_room7_mode UCHAR — RW Enum
2635 Zone 10 Raum 7 Relais zm10_room7_relay UCHAR — R Binary
2636–2637 Zone 10 Raum 8 Raumtemperatur zm10_room8_temp FLOAT °C RW —
2638–2639 Zone 10 Raum 8 Raumsolltemperatur zm10_room8_setpoint FLOAT °C RW —
2640 Zone 10 Raum 8 Raumfeuchte zm10_room8_humidity UCHAR % RW —
2641 Zone 10 Raum 8 Raumbetriebsart zm10_room8_mode UCHAR — RW Enum
2642 Zone 10 Raum 8 Relais zm10_room8_relay UCHAR — R Binary

4000+ · Navigator 10 extensions (25)

Address(es) Description (DE) Register name Type Unit Access Note
4001 Booster Störung booster_fault UCHAR — R Navigator 10, Enum
4002 Booster Verriegelung booster_interlock UCHAR — R Navigator 10
4010–4011 Booster A Wärmequelleneintritt booster_a_source_inlet_temp FLOAT °C R Navigator 10
4012–4013 Booster A Wärmequellenaustritt booster_a_source_outlet_temp FLOAT °C R Navigator 10
4014–4015 Booster A Speichertemperatur booster_a_storage_temp FLOAT °C R Navigator 10
4016–4017 Booster A Vorlauftemperatur booster_a_flow_temp FLOAT °C R Navigator 10
4018–4019 Booster A Rücklauftemperatur booster_a_return_temp FLOAT °C R Navigator 10
4020 Booster A Wärmequellenpumpe booster_a_source_pump INT16 % R Navigator 10
4021 Booster A Ladepumpe booster_a_charging_pump INT16 % R Navigator 10
4022 Booster A Verdichter booster_a_compressor UCHAR — R Navigator 10
4040–4041 Booster B Wärmequelleneintritt booster_b_source_inlet_temp FLOAT °C R Navigator 10
4042–4043 Booster B Wärmequellenaustritt booster_b_source_outlet_temp FLOAT °C R Navigator 10
4044–4045 Booster B Speichertemperatur booster_b_storage_temp FLOAT °C R Navigator 10
4046–4047 Booster B Vorlauftemperatur booster_b_flow_temp FLOAT °C R Navigator 10
4048–4049 Booster B Rücklauftemperatur booster_b_return_temp FLOAT °C R Navigator 10
4050 Booster B Wärmequellenpumpe booster_b_source_pump INT16 % R Navigator 10
4051 Booster B Ladepumpe booster_b_charging_pump INT16 % R Navigator 10
4052 Booster B Verdichter booster_b_compressor UCHAR — R Navigator 10
4108–4109 Leistungsbegrenzung Wärmepumpe power_limit_hp FLOAT kW RW Navigator 10
4112–4113 Leistungsbegrenzung Kaskade power_limit_cascade FLOAT kW RW Navigator 10
4120–4121 Firmware Version Navigator firmware_version FLOAT — R disabled by default
4122–4123 Elektrische Leistungsaufnahme Wärmepumpe power_consumption_hp FLOAT kW R —
4124–4125 Elektrische Leistungsaufnahme Smartfox power_consumption_hp_smartfox FLOAT kW R Navigator 10
4126–4127 Thermische Leistung (Durchflusssensor) thermal_power_flow_sensor FLOAT kW R —
4128–4129 Gesamte Wärmemenge (Vortex) total_heat_energy FLOAT kWh R —

Also generated from idm-heatpump-api[web]==2.6.0.

The Navigator 1.0/1.7 controllers use a different register layout: the same address can carry a different data point than in the catalog above, so this family has its own table with 156 definitions (82 writable). The official RW holding block of ma_de_812049 Rev.1 contributes 78 writable, EEPROM-sensitive parameters (operating modes, room/flow setpoints, heating curves, limits, bivalence points, solar mode, DHW setpoint); the PV supplement appears only when the controller answers address 74. No zone-module control exists on this family.

Address(es) Description (DE) Register name Type Unit Access Note
74–75 PV Überschuss pv_surplus FLOAT kW RW PV supplement
76–77 E-Heizstab Leistung electric_heater_power FLOAT kW RW PV supplement
78–79 PV Produktion pv_production FLOAT kW RW PV supplement
82–83 Hausverbrauch house_consumption FLOAT kW RW PV supplement
1000–1001 Außentemperatur outdoor_temp FLOAT °C R
1002–1003 Wärmepumpen Vorlauftemperatur hp_flow_temp FLOAT °C R
1004–1005 HGL Vorlauftemperatur B35 hgl_flow_temp FLOAT °C R
1006–1007 Wärmequellenaustritt heat_source_outlet_temp FLOAT °C R
1008–1009 Wärmespeichertemperatur storage_temp FLOAT °C R
1010–1011 Kältespeichertemperatur cold_storage_temp FLOAT °C R
1012–1013 Trinkwassererwärmer dhw_temp FLOAT °C R
1014–1015 Warmwasser Zapftemperatur dhw_tapping_temp FLOAT °C R
1016–1017 Vorlauftemperatur HK A hc_a_flow_temp FLOAT °C R
1018–1019 Vorlauftemperatur HK B hc_b_flow_temp FLOAT °C R
1020–1021 Vorlauftemperatur HK C hc_c_flow_temp FLOAT °C R
1022–1023 Vorlauftemperatur HK D hc_d_flow_temp FLOAT °C R
1024–1025 Vorlauftemperatur HK E hc_e_flow_temp FLOAT °C R
1026–1027 Vorlauftemperatur HK F hc_f_flow_temp FLOAT °C R
1028–1029 Vorlauftemperatur HK G hc_g_flow_temp FLOAT °C R
1030–1031 Raumgerätetemperatur HK A hc_a_room_device_temp FLOAT °C R
1032–1033 Raumgerätetemperatur HK B hc_b_room_device_temp FLOAT °C R
1034–1035 Raumgerätetemperatur HK C hc_c_room_device_temp FLOAT °C R
1036–1037 Raumgerätetemperatur HK D hc_d_room_device_temp FLOAT °C R
1038–1039 Raumgerätetemperatur HK E hc_e_room_device_temp FLOAT °C R
1040–1041 Raumgerätetemperatur HK F hc_f_room_device_temp FLOAT °C R
1042–1043 Raumgerätetemperatur HK G hc_g_room_device_temp FLOAT °C R
1044–1045 Heißgastemperatur hot_gas_temp FLOAT °C R
1046–1047 Feuchtesensor humidity_sensor FLOAT % R
1048–1049 Luftansaugtemperatur air_intake_temp FLOAT °C R
1050–1051 Luftwärmetauscher Temperatur air_heat_exchanger_temp FLOAT °C R
1052–1053 Solar Kollektortemperatur solar_collector_temp FLOAT °C R
1054–1055 Solar Ladetemperatur solar_charging_temp FLOAT °C R
1056–1057 Solar Kollektorrücklauftemperatur solar_collector_return_temp FLOAT °C R
1058–1059 Solar Pool / Wärmequellenreferenz solar_pool_temp FLOAT °C R
1060–1061 Gemittelte Außentemperatur outdoor_temp_avg FLOAT °C R
1062–1063 Wärmequelleneintritt heat_source_inlet_temp FLOAT °C R
1064–1065 ISC Ladefühler Kühlen isc_cooling_charge_temp FLOAT °C R
1066–1067 ISC Rückkühltemperatur isc_recooling_temp FLOAT °C R
1068–1069 Thermische Leistung WP-Vorlauf thermal_power_hp_flow FLOAT kW R
1070–1071 Thermische Leistung HGL-Vorlauf thermal_power_hgl_flow FLOAT kW R
1072–1073 Thermische Gesamtleistung thermal_power_total FLOAT kW R
1074–1075 Thermische Solarleistung thermal_power_solar FLOAT kW R
1076–1077 Wärmemenge Gesamt energy_total FLOAT kWh R
1078–1079 Wärmemenge Heizen energy_heating FLOAT kWh R
1080–1081 Wärmemenge HGL energy_hgl FLOAT kWh R
1082–1083 Wärmemenge Kühlen energy_cooling FLOAT kWh R
1084–1085 Wärmemenge Solar energy_solar FLOAT kWh R
1086–1087 Grundwasserpumpe Durchflusszähler groundwater_pump_flow_total FLOAT — R
1088–1089 Betriebsstunden Wärmequellenpumpe heat_source_pump_operating_hours FLOAT h R
1500 Störungsnummer error_number UINT16 — R
1501 Wärmepumpen Betriebsart hp_operating_mode UCHAR — R
1502 Status HK A hc_a_status UINT16 — R
1503 Status HK B hc_b_status UINT16 — R
1504 Status HK C hc_c_status UINT16 — R
1505 Status HK D hc_d_status UINT16 — R
1506 Status HK E hc_e_status UINT16 — R
1507 Status HK F hc_f_status UINT16 — R
1508 Status HK G hc_g_status UINT16 — R
1509 Verdichter 1 compressor_status_1 UINT16 — R
1510 Verdichter 2 compressor_status_2 UINT16 — R
1511 Verdichter 3 compressor_status_3 UINT16 — R
1512 Verdichter 4 compressor_status_4 UINT16 — R
1513 Ladepumpe M73 charging_pump_status UINT16 — R
1514 Wärmequellenpumpe M15 heat_source_pump_status UINT16 — R
1515 Zwischenkreispumpe Status intermediate_circuit_pump_status UINT16 — R
1516 ISC Kältespeicherpumpe M84 isc_cold_storage_pump_status UINT16 — R
1517 ISC Rückkühlpumpe M17 isc_recooling_pump_status UINT16 — R
1518 Verdichterstufen Heizen compressor_stages_heating UINT16 — R
1519 Verdichterstufen Kühlen compressor_stages_cooling UINT16 — R
1520 Verdichterstufen Warmwasser compressor_stages_dhw UINT16 — R
1521 Betriebsart Kaskade cascade_mode UINT16 — R
1522 Solar Betriebsart solar_mode UINT16 — R
1523 Smart Grid Status smart_grid_status UINT16 — R
1524 ISC Modus isc_mode UINT16 — R
2000 Betriebsart System system_mode_17 UINT16 — RW · EEPROM
2002 Betriebsart HK A hc_a_operating_mode UINT16 — RW · EEPROM
2004 Betriebsart HK B hc_b_operating_mode UINT16 — RW · EEPROM
2006 Betriebsart HK C hc_c_operating_mode UINT16 — RW · EEPROM
2008 Betriebsart HK D hc_d_operating_mode UINT16 — RW · EEPROM
2010 Betriebsart HK E hc_e_operating_mode UINT16 — RW · EEPROM
2012 Betriebsart HK F hc_f_operating_mode UINT16 — RW · EEPROM
2014 Betriebsart HK G hc_g_operating_mode UINT16 — RW · EEPROM
2016–2017 Raumsoll Heizen Normal HK A hc_a_room_setpoint_heat_normal FLOAT °C RW · EEPROM
2018–2019 Raumsoll Heizen Normal HK B hc_b_room_setpoint_heat_normal FLOAT °C RW · EEPROM
2020–2021 Raumsoll Heizen Normal HK C hc_c_room_setpoint_heat_normal FLOAT °C RW · EEPROM
2022–2023 Raumsoll Heizen Normal HK D hc_d_room_setpoint_heat_normal FLOAT °C RW · EEPROM
2024–2025 Raumsoll Heizen Normal HK E hc_e_room_setpoint_heat_normal FLOAT °C RW · EEPROM
2026–2027 Raumsoll Heizen Normal HK F hc_f_room_setpoint_heat_normal FLOAT °C RW · EEPROM
2028–2029 Raumsoll Heizen Normal HK G hc_g_room_setpoint_heat_normal FLOAT °C RW · EEPROM
2030–2031 Raumsoll Heizen Eco HK A hc_a_room_setpoint_heat_eco FLOAT °C RW · EEPROM
2032–2033 Raumsoll Heizen Eco HK B hc_b_room_setpoint_heat_eco FLOAT °C RW · EEPROM
2034–2035 Raumsoll Heizen Eco HK C hc_c_room_setpoint_heat_eco FLOAT °C RW · EEPROM
2036–2037 Raumsoll Heizen Eco HK D hc_d_room_setpoint_heat_eco FLOAT °C RW · EEPROM
2038–2039 Raumsoll Heizen Eco HK E hc_e_room_setpoint_heat_eco FLOAT °C RW · EEPROM
2040–2041 Raumsoll Heizen Eco HK F hc_f_room_setpoint_heat_eco FLOAT °C RW · EEPROM
2042–2043 Raumsoll Heizen Eco HK G hc_g_room_setpoint_heat_eco FLOAT °C RW · EEPROM
2044–2045 Heizkurve HK A hc_a_heating_curve FLOAT — RW · EEPROM
2046–2047 Heizkurve HK B hc_b_heating_curve FLOAT — RW · EEPROM
2048–2049 Heizkurve HK C hc_c_heating_curve FLOAT — RW · EEPROM
2050–2051 Heizkurve HK D hc_d_heating_curve FLOAT — RW · EEPROM
2052–2053 Heizkurve HK E hc_e_heating_curve FLOAT — RW · EEPROM
2054–2055 Heizkurve HK F hc_f_heating_curve FLOAT — RW · EEPROM
2056–2057 Heizkurve HK G hc_g_heating_curve FLOAT — RW · EEPROM
2058 Heizgrenze HK A hc_a_heating_limit UINT16 °C RW · EEPROM
2060 Heizgrenze HK B hc_b_heating_limit UINT16 °C RW · EEPROM
2062 Heizgrenze HK C hc_c_heating_limit UINT16 °C RW · EEPROM
2064 Heizgrenze HK D hc_d_heating_limit UINT16 °C RW · EEPROM
2066 Heizgrenze HK E hc_e_heating_limit UINT16 °C RW · EEPROM
2068 Heizgrenze HK F hc_f_heating_limit UINT16 °C RW · EEPROM
2070 Heizgrenze HK G hc_g_heating_limit UINT16 °C RW · EEPROM
2072 Festwertvorlauf HK A hc_a_setpoint_flow_constant UINT16 °C RW · EEPROM
2074 Festwertvorlauf HK B hc_b_setpoint_flow_constant UINT16 °C RW · EEPROM
2076 Festwertvorlauf HK C hc_c_setpoint_flow_constant UINT16 °C RW · EEPROM
2078 Festwertvorlauf HK D hc_d_setpoint_flow_constant UINT16 °C RW · EEPROM
2080 Festwertvorlauf HK E hc_e_setpoint_flow_constant UINT16 °C RW · EEPROM
2082 Festwertvorlauf HK F hc_f_setpoint_flow_constant UINT16 °C RW · EEPROM
2084 Festwertvorlauf HK G hc_g_setpoint_flow_constant UINT16 °C RW · EEPROM
2086–2087 Raumsoll Kühlen Normal HK A hc_a_room_setpoint_cool_normal FLOAT °C RW · EEPROM
2088–2089 Raumsoll Kühlen Normal HK B hc_b_room_setpoint_cool_normal FLOAT °C RW · EEPROM
2090–2091 Raumsoll Kühlen Normal HK C hc_c_room_setpoint_cool_normal FLOAT °C RW · EEPROM
2092–2093 Raumsoll Kühlen Normal HK D hc_d_room_setpoint_cool_normal FLOAT °C RW · EEPROM
2094–2095 Raumsoll Kühlen Normal HK E hc_e_room_setpoint_cool_normal FLOAT °C RW · EEPROM
2096–2097 Raumsoll Kühlen Normal HK F hc_f_room_setpoint_cool_normal FLOAT °C RW · EEPROM
2098–2099 Raumsoll Kühlen Normal HK G hc_g_room_setpoint_cool_normal FLOAT °C RW · EEPROM
2100–2101 Raumsoll Kühlen Eco HK A hc_a_room_setpoint_cool_eco FLOAT °C RW · EEPROM
2102–2103 Raumsoll Kühlen Eco HK B hc_b_room_setpoint_cool_eco FLOAT °C RW · EEPROM
2104–2105 Raumsoll Kühlen Eco HK C hc_c_room_setpoint_cool_eco FLOAT °C RW · EEPROM
2106–2107 Raumsoll Kühlen Eco HK D hc_d_room_setpoint_cool_eco FLOAT °C RW · EEPROM
2108–2109 Raumsoll Kühlen Eco HK E hc_e_room_setpoint_cool_eco FLOAT °C RW · EEPROM
2110–2111 Raumsoll Kühlen Eco HK F hc_f_room_setpoint_cool_eco FLOAT °C RW · EEPROM
2112–2113 Raumsoll Kühlen Eco HK G hc_g_room_setpoint_cool_eco FLOAT °C RW · EEPROM
2114 Kühlgrenze HK A hc_a_cooling_limit UINT16 °C RW · EEPROM
2116 Kühlgrenze HK B hc_b_cooling_limit UINT16 °C RW · EEPROM
2118 Kühlgrenze HK C hc_c_cooling_limit UINT16 °C RW · EEPROM
2120 Kühlgrenze HK D hc_d_cooling_limit UINT16 °C RW · EEPROM
2122 Kühlgrenze HK E hc_e_cooling_limit UINT16 °C RW · EEPROM
2124 Kühlgrenze HK F hc_f_cooling_limit UINT16 °C RW · EEPROM
2126 Kühlgrenze HK G hc_g_cooling_limit UINT16 °C RW · EEPROM
2128 Kühlvorlauf HK A hc_a_setpoint_flow_cooling UINT16 °C RW · EEPROM
2130 Kühlvorlauf HK B hc_b_setpoint_flow_cooling UINT16 °C RW · EEPROM
2132 Kühlvorlauf HK C hc_c_setpoint_flow_cooling UINT16 °C RW · EEPROM
2134 Kühlvorlauf HK D hc_d_setpoint_flow_cooling UINT16 °C RW · EEPROM
2136 Kühlvorlauf HK E hc_e_setpoint_flow_cooling UINT16 °C RW · EEPROM
2138 Kühlvorlauf HK F hc_f_setpoint_flow_cooling UINT16 °C RW · EEPROM
2140 Kühlvorlauf HK G hc_g_setpoint_flow_cooling UINT16 °C RW · EEPROM
2142 Externe Anforderungstemperatur Heizen external_demand_temp_heating UINT16 °C RW · EEPROM
2144 Externe Anforderungstemperatur Kühlen external_demand_temp_cooling UINT16 °C RW · EEPROM
2146 Bivalenzpunkt 1 bivalence_point_1_17 INT16 °C RW · EEPROM
2148 Bivalenzpunkt 2 bivalence_point_2_17 INT16 °C RW · EEPROM
2150 Betriebsart Solar solar_operating_mode_17 UINT16 — RW · EEPROM
2152–2153 Warmwasser Sollwert dhw_setpoint FLOAT °C RW · EEPROM
3000 Fehlerquittierung error_acknowledge BOOL — W · write-only
3001 Anforderung Heizen demand_heating_17 BOOL — R
3002 Anforderung Kühlen demand_cooling_17 BOOL — R
3003 Anforderung Vorrangladung demand_dhw_17 BOOL — R
4122–4123 Elektrische Leistungsaufnahme Wärmepumpe power_consumption_hp FLOAT kW R PV supplement